Inspection
Inspection Details
Equipment ID
18473
18473
Inspection Date
5/3/2018
5/3/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Rick Buttice
Rick Buttice
Mechanic Name
Relief Valve Pressure
640
640
Slide
Governor Rope Pull
Door Closing Force
19
19
External ID
Location
City Place 5
845 N New Ballas Court, Creve Coeur, MO
Phone: (314) 993-5800
845 N New Ballas Court, Creve Coeur, MO
Phone: (314) 993-5800
Owner
CBRE
9666 Olive Blved Suite 590, St Louis, MO 63132
9666 Olive Blved Suite 590, St Louis, MO 63132
Billing
Attn: Streamco LLC
P O Box 2021, , MI 48090
P O Box 2021, , MI 48090
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 1.16 - Rated load, platform area, and data plate | 1001.2(a)(16) | No | No | Provide a capacity data plate in the car. | 6/25/2019 |
| A17.1-1996 : Elevators | 1.12 - Car enclosure | 1001.2(a)(12) | No | No | Provide numbering of unit inside of car. | 6/25/2019 |
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | This elevator is equipped with an over speed valve. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test. | 6/1/2021 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 6/1/2021 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 8/26/2022 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 9/24/2024 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.8 Switch Keys | Yes | No | Phase 2 switch key shall not be removable in "ON" position. | 5/1/2026 |
| A17.1-1996 : Elevators | 2.8 - Pipes, wiring, and ducts | 102.2 | Yes | No | Oil coolers are wired to cab lighting circuit. Shall be dedicated circuits. | 5/1/2026 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it | 5/1/2026 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation shall be provided in the machine room. Missing PM/repair/callback/testing logs for 2023, 2024 and 2025. | 5/1/2026 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.7 Firefighter' Service Operating Procedures | No | No | Fire service testing must be documented monthly. | 5/1/2026 |