Inspection
Inspection Details
Equipment ID
5661
5661
Inspection Date
12/16/2019
12/16/2019
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Michial Linenfelser
Michial Linenfelser
Mechanic Name
Robert Kehm
Robert Kehm
Relief Valve Pressure
Slide
24"
24"
Governor Rope Pull
210/770
210/770
Door Closing Force
26
26
External ID
9a5b8800-d41c-400d-b9a5-f0143ce1dd0b
9a5b8800-d41c-400d-b9a5-f0143ce1dd0b
Location
OLTUC Bldg
1139 OLIVE ST, SAINT LOUIS, MO
Phone: (314) 486-5623
1139 OLIVE ST, SAINT LOUIS, MO
Phone: (314) 486-5623
Owner
First Morgan LLC
727 N 1ST ST STE 400, SAINT LOUIS, MO 63102-2542
727 N 1ST ST STE 400, SAINT LOUIS, MO 63102-2542
Billing
Attn: First Morgan LLC
727 N 1ST ST STE 400, SAINT LOUIS, MO 63102-2542
727 N 1ST ST STE 400, SAINT LOUIS, MO 63102-2542
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | The elevator machine room cannot be used for storage. Remove the items (old AC units) being stored in the machine room to provide proper room for maintenance to be performed. | 7/10/2018 |
| conversion | conversion | n/a | No | No | The fire extinguisher in the machine room needs to be serviced, the last annual service tag indicates it was serviced in 2016. | 7/10/2018 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone line does not work | 3/25/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.2 Replacement of Suspension Means (Re-Inspection) | Yes | Yes | Suspension ropes are showing rouge and the diameter has reduced beyond the maximum allowable amount. Replace suspension ropes. | 5/14/2025 |
| A17.1-2016 : Elevators | 2.13 - Governor, Overspeed Switch, and Seal | 8.6.4.20.2 | Yes | Yes | The pullout is higher than the pull through of the governor. The safetiies releasing carrier does not pull out when the jaw is fully set. | 5/14/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | When a car is outside the unlocking zone, the car doors shall be so arranged that when in the closed position they shall be restricted from opening | 5/14/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.2.5 Rope Tension (Re-Inspect) | Yes | No | Replace the broken springs located on the suspension rope shackles and tension the ropes | 5/14/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | The anti-rotation cable on the car side suspension shackles is frayed and coming apart. Replace the anti-rotation cable. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Provide a governor rope data tag | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Inspection incomplete. Need to test pullout/pull through, set the safeties with a full load, fire service, 110 back up power, counter weight buffer, and emergency phone | 5/14/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | When a car is outside the unlocking zone, the car doors shall be so arranged that when in the closed position they shall be restricted from opening. | |
| A17.1-2016 : Elevators | 3.20 - Governor rope | 8.7.3.16 | Yes | No | 8.7.2.19 - Provide a Governor rope data tag (2.18.5.3) |