Inspection
Inspection Details
Equipment ID
19283
19283
Inspection Date
5/3/2018
5/3/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Rick Buttice
Rick Buttice
Mechanic Name
Relief Valve Pressure
465
465
Slide
Governor Rope Pull
Door Closing Force
21
21
External ID
Location
City Place 5
845 N New Ballas Court, Creve Coeur, MO
Phone: (314) 993-5800
845 N New Ballas Court, Creve Coeur, MO
Phone: (314) 993-5800
Owner
CBRE
9666 Olive Blved Suite 590, St Louis, MO 63132
9666 Olive Blved Suite 590, St Louis, MO 63132
Billing
Attn: Streamco LLC
P O Box 2021, , MI 48090
P O Box 2021, , MI 48090
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
A17.1-1996 : Elevators | 1.12 - Car enclosure | 1001.2(a)(12) | Provide numbering of unit inside car. | 6/25/2019 | ||
A17.1-1996 : Elevators | 2.2 Headroom | 1001.2(b)(2) | Provide guard on bulbs in machine room. | 6/25/2019 | ||
A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test. | 6/1/2021 | ||
A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 6/1/2021 | ||
A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) | x | The in car emergency lighting shall be operational. | 8/15/2022 | |
A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 8/26/2022 | ||
A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 9/24/2024 | ||
A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | x | Battery lowering shall work. | ||
A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | |||
A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | A code compliant MCP and related on-site documention shall be provided in the machine room. Missing PM/repair/callback/testing logs for 2023, 2024 and 2025. | |||
A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1206.1h | Machine room shall have proper fire extinguisher and shall have monthly/annual test tag. | |||
A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1206.7 | Fire service testing must be documented monthly. |