Inspection
Inspection Details
Equipment ID
19428
19428
Inspection Date
5/4/2018
5/4/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Paul Karrenbrock
Paul Karrenbrock
Mechanic Name
Relief Valve Pressure
Slide
Governor Rope Pull
Door Closing Force
21
21
External ID
Location
Hawkeye Hotels
1019 Pine St, St. Louis, MO
Phone: (314) 436-2355
1019 Pine St, St. Louis, MO
Phone: (314) 436-2355
Owner
Hawkeye Hotels
1019 Pine St, St. Louis, MO 63101
1019 Pine St, St. Louis, MO 63101
Billing
Attn: Hawkeye Hotels
1019 Pine St, , MO 63101
1019 Pine St, , MO 63101
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Afix brake data tag permenetly to machine by brake assembly | |
| conversion | conversion | n/a | No | No | Install rope gripper device | |
| conversion | conversion | conversion - reinspect | Yes | No | Perform all necessary alteration testing | 5/4/2018 |
| conversion | conversion | n/a | No | No | Provide a afix alteration data tag to controller | |
| conversion | conversion | n/a | No | No | Provide earth ground for machine support beams isolated from machine assembly | |
| conversion | conversion | n/a | No | No | Install rope gripper | |
| conversion | conversion | n/a | No | No | Pit should be clean and dry remove water and debris | |
| conversion | conversion | n/a | No | No | Machine room door should be self closing and self locking | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | The lighting in the elevator cab has been damaged and shall be repaired to at least provide not less than five (5) foot-candles of lighting throughout the cab. | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | The cab ceiling is of the open type, which does not provide protection from the light bulbs should they shatter. The lights shall be guarded by plastic sleeve or some other means to properly protect passengers. | |
| MO Minimum : Elevators | (F) - Electrical Switches | (F)1 | Yes | No | The stop switch in the elevator toggle is broken and will not operate properly. Repair or replace switch. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | The elevator telephone inside the elevator is not working properly. Check and repair the phone line of this phone for proper operation and passenger safety. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | The tops of cars shall be kept free of dirt, and rubbish. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)2 Alterations | No | No | There is no code data plate found on the equipment to indicate the code and edition that the elevator was altered to, as used for all inspections. Provide a proper plate on the front of the controller or mainline disconnect. With the alteration of the driving machine, it shall state the specific devices that were altered and which code it should be referenced for inspection purposes. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)2 Alterations | No | No | When an alteration of the drive machine is performed it shall conform to all the requirements of A17.1 2004 section 8.7.2.25.1 which also includes (but not limited to) a rope gripping device. | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | The elevator machine room door shall be self-closing and self-locking and shall be operable from the interior space without the use of a key. | |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The elevator pit shall be cleaned of dust and debris. | |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | No | The fireman's emergency service phase I and II operations was tested and the following deficiency was noted:The smoke sensors are not hooked up to the elevator controllers for phase I recall operation. The building is unoccupied and under revitalization with an upgraded fire alarm panel. Reinspection is required. | |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | No | The fireman's emergency service phase I and II operations was tested and the following deficiency was noted:There is no fireman’s emergency service phase I instruction signage adjacent to the keyed switch at the primary egress floor, as required. | |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | No | The fireman's emergency service phase I and II operations was tested and the following deficiency was noted:There is no “In Case of Fire Use Stairs” signage at each landing as required. | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | The current state operating certificate needs to be posted in the machine room in a noncombustible frame. |