Inspection
Inspection Details
Equipment ID
977
977
Inspection Date
4/26/2018
4/26/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Thomas McGrath
Thomas McGrath
Mechanic Name
Relief Valve Pressure
400
400
Slide
NA
NA
Governor Rope Pull
NA/NA
NA/NA
Door Closing Force
Front 25 Rear 12
Front 25 Rear 12
External ID
977
977
Location
Bank of America Concord Plaza
5353 S Lindbergh Blvd, St. Louis, MO
Phone: (314) 248-3760
5353 S Lindbergh Blvd, St. Louis, MO
Phone: (314) 248-3760
Owner
Ariel investment LLC
717 The Hamptons Lane, Town & Country, MO 63017
717 The Hamptons Lane, Town & Country, MO 63017
Billing
Attn: Ariel investment LLC
Yuhling Lu
8825 Page Ave, , MO 63114
Yuhling Lu
8825 Page Ave, , MO 63114
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Post current State certificate in machine room | 4/18/2019 |
| conversion | conversion | n/a | No | No | Repair electric eye on front car door | 4/18/2019 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State certificate in machine room | 4/18/2019 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | No | No | Photo eye on the car door is functional during fire service recall. Photo eye must be overridden during fire service Phase 1 and 2. | 3/19/2021 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 7/7/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The pit shall be kept clean and dry. The pit needs to be cleaned. | 7/7/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Cylinder packing is worn and leaking, repair/ replace as needed. | 4/20/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Observed standing water in the pit, confirm sump pump is working, if not-replace. | 4/20/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 4/20/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Water shall not be allowed to accumulate in the pit. This is a multi-year violation. If not corrected by next annual inspection a re-inspection will be required. | 4/20/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)8 | No | No | Sump pump and cover has been removed and shall be replaced. | 4/20/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | No MO State operating certificate in the machine room. |