Inspection
Inspection Details
Equipment ID
14318
14318
Inspection Date
11/26/2019
11/26/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Edward Balsat
Edward Balsat
Mechanic Name
John Ryan
John Ryan
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
18
18
External ID
45514b63-d2cd-425e-809e-e5a1d0edc0fc
45514b63-d2cd-425e-809e-e5a1d0edc0fc
Location
Charter Senior Living
6543 CHIPPEWA ST, SAINT LOUIS, MO
Phone: (000) 000-0000
6543 CHIPPEWA ST, SAINT LOUIS, MO
Phone: (000) 000-0000
Owner
Attn: Charter Senior Living
Charter Senior Living
6543 CHIPPEWA ST, SAINT LOUIS, MO 63109
Phone: (314) 647-6600
Email: ed@charterstlouishills.com
Charter Senior Living
6543 CHIPPEWA ST, SAINT LOUIS, MO 63109
Phone: (314) 647-6600
Email: ed@charterstlouishills.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.5 - Access to Hoistway | 8.11.2.1.4(e) | Yes | No | Make top floor access switch operational. | 11/26/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.16 - Traveling cables and junction boxes | 8.11.2.1.3(v) | Yes | No | Secure all hoistway junction box covers. | 11/26/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.11.2.1.2(e) (Re-Inspection) | Yes | No | Remove all unused and old equipment from the machine room. | 11/26/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.11.2.1.4(l) | Yes | Yes | Make flashing fire hat operational. | 11/26/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.11 - Disconnecting Means and Control | 2.26.4 | Yes | No | Provide permanent wiring for 110v source to controller. | 11/26/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.8 - Pipes, wiring, and ducts | 8.11.2.1.2(h) | Yes | No | Secure all duct and junction box covers and secure all conduit runs. | 11/26/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display a copy of the current state operating certificate. | 3/18/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO state operating certificate shall be posted in the elevator machine room. | 12/15/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 1/11/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures are missing. (This item is for notification purposes for future violation in 2022) | 11/16/2021 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Inspection incomplete due to counterweight safeties not releasing. Only able to run the hoistway. All other items of the annual inspection and category 5 test need to be completed. | 7/8/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.17 - Drive machine brake | 8.6.4.19.11 A17.1 2016 Ascending Overspeed Protection, Unintended Movement Devices, and Emg Brake | Yes | Yes | Rope gripper is not working. Elevator Red Tagged. | 8/13/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Safety slide measurement of car and counterweight shall be obtained. | 8/13/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO state operating certificate shall be displayed in the elevator machine room. | 5/26/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | A current MCP is required in the machine room for each unit including maintenance, repair, and fire service testing logs. | 5/26/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | A current ABC rated fire extinguisher shall be provided in the machine room. | 5/26/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Audible signal and emergency car illumination not working properly when 110v power is disconnected. | 2/10/2026 |