Inspection
Inspection Details
Equipment ID
5636
5636
Inspection Date
6/6/2018
6/6/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
John Ryan
John Ryan
Mechanic Name
Relief Valve Pressure
Slide
Governor Rope Pull
Door Closing Force
External ID
Location
Monsanto Parking Garage Stair Tower A Level 1
700 Chesterfield Pkwy W, Chesterfield, MO
Phone: (636) 737-2922
700 Chesterfield Pkwy W, Chesterfield, MO
Phone: (636) 737-2922
Owner
CBRE % Monsanto
700 Chesterfield Pkwy West, Chesterfield, MO 63017
700 Chesterfield Pkwy West, Chesterfield, MO 63017
Billing
Attn: Monsanto
700 Chesterfield Parkway North, , MO 63017
700 Chesterfield Parkway North, , MO 63017
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | New hoistway penetrations shall be sealed (at the top floor). | 6/21/2019 |
| conversion | conversion | n/a | No | No | Wiring not related to the elevator shall not be added to the hoistway (at the top floor). | 6/21/2019 |
| conversion | conversion | n/a | No | No | A 2nd heat detector is required withing 24" of the second fire sprinkler head in hoistway overhead. | 6/21/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | 2.2.3 - Safety screen mesh shall be installed between two hoistways. Passenger hydraulic on backside of freight car shall have a divider. | 6/27/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Up to date operating certificate is required in the machine room. | 6/27/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | Yes | No | Some of the machine room walls have been torn down and are missing. It's currently open and without a door. The elevator machine and control equipment shall be located in a separate room or separated space designed as an elevator machine room or space and shall be accessible only to authorized personnel. | 1/21/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | Yes | No | All rooms or enclosures shall have a self-closing and self-locking door and shall be operable from the interior space without the use of a key. | 1/21/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 6/27/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | The in-car emergency light shall be operational. | 1/21/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Equipment in the machine room not being used in conjunction with the function or use of the elevator shall be removed. | 6/27/2025 |
| MO Minimum : Elevators | (J) - Counterweights | (J)2 | Yes | No | Counterwight is on springs when car reached top final limit. Runby must be a minimum of 6 inches". Suspension ropes must be shortenend. |