Inspection
Inspection Details
Equipment ID
17889
17889
Inspection Date
12/5/2019
12/5/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Gary Beadle
Gary Beadle
Mechanic Name
John Hambrough
John Hambrough
Relief Valve Pressure
520
520
Slide
Governor Rope Pull
Door Closing Force
20F/24R
20F/24R
External ID
80d33d0b-0982-4ccd-b341-9a2ad7b28cce
80d33d0b-0982-4ccd-b341-9a2ad7b28cce
Location
Islamic Center of Greater St. Louis
517 WEIDMAN RD, MANCHESTER, MO
Phone: (636) 394-7878
517 WEIDMAN RD, MANCHESTER, MO
Phone: (636) 394-7878
Owner
Attn: UNK
Islamic Center of Greater St. Louis
517 WEIDMAN RD, MANCHESTER, MO 63011
Phone: (636) 394-7878
Email: admin@islamicfoundationstl.org
Islamic Center of Greater St. Louis
517 WEIDMAN RD, MANCHESTER, MO 63011
Phone: (636) 394-7878
Email: admin@islamicfoundationstl.org
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | In cab emergency telephone shall work. | 12/20/2018 |
| A17.1-1996 : Elevators | 3.9 - Floor and emergency identification numbering | 1001.2(c)(15) | No | No | Provide elevator numbering on the car top. | 7/1/2020 |
| A17.1-1996 : Elevators | 1.12 - Car enclosure | 211.9 | No | No | Provide numbering inside the car for emergency identification. | 7/1/2020 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display a copy of the current state operating certificate. | 7/1/2020 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | All the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 3/20/2021 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational on auxiliary power. | 2/11/2022 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be obtained and displayed in the elevator machine room. | 3/20/2021 |
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test. | 3/20/2021 |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1001.2(b)(7) | No | No | A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room. | 3/20/2021 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) | Yes | No | The in car emergency lighting shall be operational. | 2/11/2022 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1206.7 | No | No | A record of findings for firefighters' service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be available on-site. Log is present but not being kept up on a monthly basis. | 1/5/2022 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Written evacuation procedures for elevators by authorized persons and emergency personnel shall be available on-site. | 1/5/2022 |
| A17.1-1996 : Elevators | 2.14 - Code data plate | 215 | No | No | Install a code data plate. It shall read A17.1-1996. | 1/5/2022 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 1/5/2022 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | No | No | Clean the pit of dirt and debris. | 1/5/2022 |
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspection) | Yes | No | This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve. The valve shall be sealed and tagged after the category 5 test. | 2/1/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (2)(C) Re-Inspection Required to Enforce. | Yes | No | There is a temporary jumper wire in the control panel, it is labeled installed in 2005. Verify if this wire is required and take the necessary corrective action. Temporary wiring and insulators or blocks in the armatures or poles of magnetically operated switches, contactors, or relays on equipment in service are prohibited. | 2/1/2023 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1206.7 | No | No | A record of findings for firefighters' service operation, tested monthly as required by 8.6.11.1 with identification of the person(s) that performed the operation, and the date shall be available on-site. | 3/2/2026 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 3/2/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) | Yes | No | The unsealed over-speed valve shall be tested with the rated load. This is the 3rd notice about the over-speed valve. The valve shall be tested within 90 days or the elevator will be locked out of service. | 4/3/2024 |
| A17.1-1996 : Elevators | 2.1 - Access to machine space | 101.3d | No | No | The machine room door shall be self-closing, self-locking and shall be operable from the interior space without the use of a key. | 3/2/2026 |
| A17.1-1996 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 111.5 Restricted Opening of Hall/Car Doors | Yes | No | The car door shall be restricted from opening when in the closed position anywhere outside the unlocking zone. | 4/3/2024 |
| A17.1-1996 : Elevators | 2.14 - Code data plate | 215 | No | No | Install a code data plate. It shall read "A17.1-1996". | 3/2/2026 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 4/16/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) | Yes | No | The unsealed over-speed valve shall be tested with the rated load. This is the 4th notice about the over-speed valve. | 4/16/2025 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 3/2/2026 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | No | No | Pit shall have code compliant lighting. | 3/2/2026 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1 | No | No | Pit shall be kept clean. | 3/2/2026 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display a copy of the current State operating certificate in the machine room. | 6/11/2026 |