Inspection
Inspection Details
Equipment ID
21377
21377
Inspection Date
12/18/2019
12/18/2019
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
James Mueller
James Mueller
Mechanic Name
Don McFadden, Jr.
Don McFadden, Jr.
Relief Valve Pressure
Slide
3"
3"
Governor Rope Pull
60/NA
60/NA
Door Closing Force
NA
NA
External ID
2bb5990f-6b58-4625-9d02-488e6747dc31
2bb5990f-6b58-4625-9d02-488e6747dc31
Location
Chemline Inc
5151 NATURAL BRIDGE AVE, SAINT LOUIS, MO
Phone: (314) 664-2230
5151 NATURAL BRIDGE AVE, SAINT LOUIS, MO
Phone: (314) 664-2230
Owner
Chemline Inc
5151 NATURAL BRIDGE AVE, SAINT LOUIS, MO 63115-1504
5151 NATURAL BRIDGE AVE, SAINT LOUIS, MO 63115-1504
Billing
Attn: Chemline Inc
5151 NATURAL BRIDGE AVE, SAINT LOUIS, MO 63115-1504
5151 NATURAL BRIDGE AVE, SAINT LOUIS, MO 63115-1504
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
conversion | conversion | n/a | Replace electrical conduit on side of car | 7/25/2018 | ||
conversion | conversion | n/a | Cover junction box on car top | 7/25/2018 | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | Fire extinguisher needs to be serviced. | 12/11/2018 | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | Provide a current tested fire extinguisher in the elevator machine room. | 3/8/2022 | ||
MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | The machine room door shall be self-closing and self-locking. | 3/8/2022 | ||
MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | A permanent lighting fixture shall be provided in all pits to provide illumination of not less then 5 ftc at the pit floor. | 3/8/2022 | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | Provide a code compliant MCP including onsite documents. | 3/8/2022 | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures are missing. (This item is for notification purposes for future violation in 2022) | 3/7/2022 | ||
MO Minimum : Elevators | (M) - Car Safeties and Speed Governors | (M)4 | x | x | The movement of the safety drum rope, starting from a fully retracted position, must not exceed 42 inches (it pulled out approximately 120 inches) before the safety shoes contact the rail. Elevator Red Tagged. | 10/10/2022 |
MO Minimum : Elevators | (I) - Pits | (I)1 | Water and oil shall not be allowed to accumulate on the pit floors. Note: The pit floor is covered with several inches of water. | 3/14/2023 | ||
MO Minimum : Elevators | (A) - Hoistways | (A)16 | All electrical wiring in the hoistway shall be enclosed in metal conduit, flexible conduit, metal raceway, or be in compliance with NFPA70. Note: There are bare wires running throughout the hoistway. | 3/14/2023 | ||
MO Minimum : Elevators | (A) - Hoistways | (A)16 | The missing junction box covers in the hoistway shall be replaced. | 3/14/2023 | ||
MO Minimum : Elevators | (A) - Hoistways | (A)12 | The penetrations in the hoistway shall be sealed with approved materials. | 3/14/2023 | ||
MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | The fluorescent pit light shall be operational and permanently wired. Note: The fixture is currently attached to a cord which runs through a hole in the hoistway wall and is plugged into an extension cord. | 3/14/2023 | ||
MO Minimum : Elevators | (C) - Car Enclosure: Freight | (C)5 | Properly secure cab lights to ceiling. |