Inspection
Inspection Details
Equipment ID
7153
7153
Inspection Date
12/12/2019
12/12/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Herbert Neulist
Herbert Neulist
Mechanic Name
Jeff Setchfield
Jeff Setchfield
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
25
25
External ID
b188fcd4-d6d7-49ec-a60b-124e3f27bd7f
b188fcd4-d6d7-49ec-a60b-124e3f27bd7f
Location
HoteLumiere
901 N 1ST ST, SAINT LOUIS, MO
Phone: (314) 881-7777
901 N 1ST ST, SAINT LOUIS, MO
Phone: (314) 881-7777
Owner
Attn: UNK
Pinnacle Entertainment
3800 HOWARD HUGHES PKWY, LAS VEGAS, NV 89169
Phone: (000) 000-0000
Pinnacle Entertainment
3800 HOWARD HUGHES PKWY, LAS VEGAS, NV 89169
Phone: (000) 000-0000
Billing
Attn: HoteLumiere
HoteLumiere
901 N 1ST ST, SAINT LOUIS, MO 63102
Phone: (314) 881-7870
Email: Maiazzi@lumiereplace.com
HoteLumiere
901 N 1ST ST, SAINT LOUIS, MO 63102
Phone: (314) 881-7870
Email: Maiazzi@lumiereplace.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Machine room lights out, repair | 2/26/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Machine leaking oil in hoistway. | 11/26/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Machine room lights need repair. 10 ft candle minimum | 11/26/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display updated current operating certificate in machine room. | 11/26/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Emergency light lens needs to be replaced. | 11/26/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Machine room lights shall be 10 ft candles. | 11/26/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency light & alarm bell not working. Re-inspection required | 12/20/2022 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Lighting in the machine room is inadequate, repair existing light fixtures and add additional lighting in front of controller to provide at least 10 fc at floor | 11/26/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Machine leaks oil onto floor, into hoistway, need to repair same | 11/26/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 11/26/2025 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | Yes | Doors do not open when recalled in Fire Fighters Emergency Service, runs between 1 and 2 without opening doors, even using door button. Red-tagged, Re-inspection required | 2/13/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Lighting in machine room is inadequate, repair existing light fixtures and add additional lighting in front of controller to provide at least 10 fc at floor | 11/26/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Machine leaks oil onto floor, into hoistway, needs repaired | 11/26/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | Yes | No | Inside of car call buttons are inoperable and shall be repaired to ensure safety for all elevator use. | 9/18/2024 |
| A17.1-2016 : Elevators | 6.3 - Firefighters' service (A17.1-1984 through A17.1a-1988 and A17.3) | 8.6.11.1 Firefighters’ Emergency Operation | Yes | Yes | Phase 1 recall inoperable and shall be repaired to meet the correct fire service requirements. | 9/18/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.8 Cleaning of Machine Rooms and Machinery Spaces | No | No | Machin Needs Cleaned | 1/17/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Car Top inspection station not working properly. Up button does not work. | 1/17/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency Light and bell not working | 1/17/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Car top needs cleaned (oil and pigmat) | 1/17/2026 |