Inspection
Inspection Details
Equipment ID
21286
21286
Inspection Date
1/2/2020
1/2/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Timothy Trout
Timothy Trout
Mechanic Name
Relief Valve Pressure
420
420
Slide
Governor Rope Pull
Door Closing Force
12
12
External ID
8f97c598-3ce3-45c5-879d-aaf1226d059a
8f97c598-3ce3-45c5-879d-aaf1226d059a
Location
Jasper Products LLC
3877 E 27TH ST, JOPLIN, MO
Phone: (417) 206-3333
3877 E 27TH ST, JOPLIN, MO
Phone: (417) 206-3333
Owner
Jasper Products LLC
3877 E 27TH ST, JOPLIN, MO 64804-3306
3877 E 27TH ST, JOPLIN, MO 64804-3306
Billing
Attn: Jasper Products LLC
3877 E 27TH ST, JOPLIN, MO 64804-3306
3877 E 27TH ST, JOPLIN, MO 64804-3306
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Reprogram the emergency phone. The old monitoring co has disccontinued your service. | 1/2/2020 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2 Design and Construction of Pits | Clean up the oil in the pit. | 3/2/2020 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.6 - Ventilation | 8.11.2.1.2(f) | REpair or add more AC to the machine room as the manufacturer requires it to be maintained at 1 to 40 degrees centigrade. It is above 120 degrees today and it is 18 degrees outside. | 3/2/2020 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.11.2.1.2(g) | Have the fire extinguisher re-certified. | 3/2/2020 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Obtain and display a current state operating certificate in the machine room | 3/2/2020 | ||
| MO Minimum : Elevators | (I) - Pits | (I)1 | Remove dirt and rubbish from pit floor | 3/24/2023 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.6 - Ventilation | 2.7.5.2 | Machine room ventilation system is not functioning correctly, provided working AC unit | 2/27/2024 | ||
| MO Minimum : Elevators | (I) - Pits | (I)1 | Pit shall be kept free of dirt and rubbish | 2/27/2024 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | remove dirt and rubbish from pit floor | 3/16/2026 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.6 - Ventilation | 8.11.2.1.2(f) | Provide operational machine room ventilation , currently over 115 degrees | 3/16/2026 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | x | MUST CLEAN PIT | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.6 - Ventilation | 8.11.2.1.2(f) | MUST PROVIDE OPERATIONAL VENTILATION | |||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.23 - Suspension rope | 8.11.2.1.3(cc) | x | ROPES MUST BE REPLACED DUE TO ROUGE |