Inspection
Inspection Details
Equipment ID
10054
10054
Inspection Date
12/17/2019
12/17/2019
Inspection Type
Reinspection
Reinspection
Inspector Name
Kurt Zimmerman
Kurt Zimmerman
Mechanic Name
Robert Kehm
Robert Kehm
Relief Valve Pressure
Slide
4"
4"
Governor Rope Pull
NA
NA
Door Closing Force
NA
NA
External ID
b4ecce84-4ed4-4aeb-9071-88f0051940b0
b4ecce84-4ed4-4aeb-9071-88f0051940b0
Location
Barry-Wiehmiller
8020 FORSYTH BLVD, CLAYTON, MO
Phone: (314) 862-8000
8020 FORSYTH BLVD, CLAYTON, MO
Phone: (314) 862-8000
Owner
Barry-Wiehmiller Companies, INC.
8020 FORSYTH BLVD, CLAYTON, MO 63105-1707
8020 FORSYTH BLVD, CLAYTON, MO 63105-1707
Billing
Attn: Barry-Wiehmiller Companies, INC.
8020 FORSYTH BLVD, CLAYTON, MO 63105-1707
8020 FORSYTH BLVD, CLAYTON, MO 63105-1707
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (M) - Car Safeties and Speed Governors | (M)1 | Yes | Yes | Test car safeties with rated load. | 12/17/2019 |
| MO Minimum : Elevators | (D) - Brakes | (D)1 | Yes | Yes | Test brake with 125% of rated load. Reinspect within 30 days. | 12/17/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Written maintenance control program shall be kept on site for each elevator. | 10/10/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 6/29/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Test incomplete, need to perform the following test to complete inspection: Pull out and pull through force of governor, test tripping speeds of governor overspeed switch and governor jaws, unintended movement test with 125% of rated load, traction drive machine brake test with 125% of rated load & test car safeties with rated load at rated speed. Re-inspection required | 1/20/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Elevator cab phone does not work. Re-inspection required | 1/20/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current operating certificate shall be displayed in the elevator machine room | 10/10/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | Yes | No | Water is entering pit and causing counterweight buffer stand, car buffer, and bottom of rails to rust. Shall be repaired to prevent further rust and damage. | |
| MO Minimum : Elevators | (I) - Pits | (I)5 | No | No | Pit ladders is rusted through where it bolts to floor. Shall be repaired. | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Phone not working. Line voltage is not present in elevator machine room. |