Inspection
Inspection Details
Equipment ID
18094
18094
Inspection Date
6/30/2017
6/30/2017
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Unknown Conversion
Unknown Conversion
Mechanic Name
Relief Valve Pressure
380
380
Slide
Governor Rope Pull
Door Closing Force
21
21
External ID
Location
Carthage High School
2600 S. River St, Carthage, MO
Phone: (417) 359-7015
2600 S. River St, Carthage, MO
Phone: (417) 359-7015
Owner
Carthage R-9 School District
710 S Lyon St, Carthage, MO 64836
710 S Lyon St, Carthage, MO 64836
Billing
Attn: Carthage R-9 School District
710 S Lyon St, , MO 64836
710 S Lyon St, , MO 64836
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | Alarm does not work--reinspect required | 7/5/2018 |
| conversion | conversion | n/a | No | No | Emergency light needs battery | 7/5/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | needs current certificate posted | 12/22/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | 2-way communication device shall give proper location message, unresponsive on battery power(REINSPECTION REQUIRED) | 6/10/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Repair/replace broken 1st floor hall button | 1/5/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | MCP shall be kept in equipment room, including Oil loss log and Fire service testing log, recorded monthly. | 1/5/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | 2021&2022 VIO: Compliant/Required Documentation & MCP shall be kept in equipment room(neat/organized) including Wiring Diagrams, Oil log &Fire service log, recorded monthly. (Provided by Elev Co.) | 12/22/2022 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Clean Pit | 12/22/2022 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | 11 CSR 40-5.100(2) : Current State Operating Permit shall be displayed in the Equipment Room in a non-combustible frame. (Mounted to wall preferred) MOST CURRENT CERTIFICATE EXPIRED 2018. | 12/22/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | 2-way communication device shall give proper location message, unresponsive on battery power(REINSPECTION REQUIRED) | 6/10/2022 |