Inspection
Inspection Details
Equipment ID
2806
2806
Inspection Date
1/3/2020
1/3/2020
Inspection Type
Reinspection
Reinspection
Inspector Name
Jerry Eckhart
Jerry Eckhart
Mechanic Name
Joseph Wuelling
Joseph Wuelling
Relief Valve Pressure
Slide
Na
Na
Governor Rope Pull
330/700
330/700
Door Closing Force
NA
NA
External ID
933ad892-fe3e-46e2-9a55-65a56ceb4d08
933ad892-fe3e-46e2-9a55-65a56ceb4d08
Location
SSM-St. Joseph Health Center
300 1ST CAPITOL DR, SAINT CHARLES, MO
Phone: (636) 947-5000
300 1ST CAPITOL DR, SAINT CHARLES, MO
Phone: (636) 947-5000
Owner
Attn: Marie O'Donnell
SSM St. Joseph Health Care
300 1ST CAPITOL DR, SAINT CHARLES, MO 63301
Phone: (314) 989-6134
Email: marie.odonnell@ssmhealth.com
SSM St. Joseph Health Care
300 1ST CAPITOL DR, SAINT CHARLES, MO 63301
Phone: (314) 989-6134
Email: marie.odonnell@ssmhealth.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (M) - Car Safeties and Speed Governors | (M)8 | x | x | Upon performing the required five year full load, the elevator safety governor was found to be worn to a degree that the mechanical and electrical protection devices would not activate within the required limits. Repair or replacement of the governor is required and a reinspection shall be performed before the elevator can be returned to service. | 1/3/2020 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | The testing has not been completed on the elevator at this time. The weight test shall be performed, safeties set, and buffers compressed before the inspection is completed. | 1/3/2020 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.2.5 Rope Tension (Re-Inspect) | x | The hoist rope tension is unequal due to the anti-rotational device being broken. Redistribute tension properly and repair anti-rotational device to maintain equal tension on all hoisting ropes. | 11/7/2024 | |
| MO Minimum : Elevators | (I) - Pits | (I)1 | Pit needs to be cleaned | |||
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | Pit light is not working | |||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | Need to replace bottom right counterweight guide roller | |||
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | x | Hoist ropes are rouged and undersized. Need to aquire alteraion permit and replace ropes within 60 days and perform alteration inspection. Re-inspection required | 12/13/2024 | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Provide & install test tag permanently marked with test data on all appropriate equipment. Re-inspection required | 12/13/2024 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | The anti-rotational device on the counterweight fastening hitch for the hoist ropes is broken and shall be replaced to keep the hoist ropes from spinning. | |||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | The anti-rotational device on the counterweight fastening hitch for the hoist ropes is broken and shall be replaced to keep the hoist ropes from spinning | |||
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | Light in pit shall work | |||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | Replace the bottom right counterweight guide roller | |||
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | x | Hoist ropes are rouged and undersized. Acquire alteration permit and replace ropes within 60 days and perform alteration inspection. Re-inspection required | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.7.2 Periodic Test Record (Test Tags) | Provide and install test tags permanently marked with test data on all appropriate equipment |