Inspection
Inspection Details
Equipment ID
24654
24654
Inspection Date
12/16/2019
12/16/2019
Inspection Type
New Installation
New Installation
Inspector Name
Gary Beadle
Gary Beadle
Mechanic Name
Shane Warth
Shane Warth
Relief Valve Pressure
Slide
Instantaneous
Instantaneous
Governor Rope Pull
50/225
50/225
Door Closing Force
26F/27R
26F/27R
External ID
9e1e4159-1ff5-4c91-9250-936debc228b4
9e1e4159-1ff5-4c91-9250-936debc228b4
Location
Farifield Inn & Suites
2144 Market Street, St. Louis, MO
Phone: (000) 000-0000
2144 Market Street, St. Louis, MO
Phone: (000) 000-0000
Owner
Attn: Equis Hospitality Management
Equis Hospitality Management
1401 S. Brentwood Blvd, Ste 575, Brentwood, MO 63114
Phone: (000) 000-0000
Email: kelly.bigby@kone.com
Equis Hospitality Management
1401 S. Brentwood Blvd, Ste 575, Brentwood, MO 63114
Phone: (000) 000-0000
Email: kelly.bigby@kone.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 8.11.2.1.2(c) | Yes | No | Provide code compliant machine room lighting at top floor. Measured at 14.4fc. | 12/23/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational with 24/7 support. | 12/23/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.8 - Hoistway enclosure | 8.11.2.1.4(h) | Yes | No | Seal all hoistway penetrations. | 12/23/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2 Design and Construction of Pits | Yes | No | Provide the sump hole with a cover. | 12/23/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.5 Illumination of Pits | Yes | No | Provide code compliant pit lighting. Measured at 4.4fc. | 12/23/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The emergency phone shall identify the correct car number. | 1/22/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 6/9/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.16 - Traveling cables and junction boxes | 8.11.2.1.3(v) | No | No | The traveling cables shall be installed using an approved method. Currently hung incorrectly under the car. | 6/9/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 8.11.2.1.1(q) | Yes | No | 8.6.1.7.5 - The emergency rescue device shall be operational. | 6/10/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 6/9/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.11.2.1.4(l) | Yes | Yes | The rear open and close buttons in the car firefighters operation panel, and the rear door close button shall be operational on phase 2 fire service. - Elevator Red Tagged. | 6/10/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.13 - Governor,overspeed switch and seal | 8.11.2.1.2(bb) | Yes | No | The remote governor tripping means on the controller shall be operational. | 6/10/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.2 - Hoistway doors | 8.6.4.13 | Yes | No | Hoistway doors are missing safety retainers. The top and bottom of horizontally sliding doors shall be provided with a means of retaining the closed door panel in position if the primary guiding means fail. | 12/14/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Hoistways and pits shall be kept free of dirt and rubbish and shall not be used for storage purposes. Clean the pit. | 6/14/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone personnel couldn't repeat location of elevator. Two-way communications shall be directed to a location(s) staffed by authorized personnel who can take appropriate action. | 12/14/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The emergency phone is still not working. Emergency phone personnel couldn't repeat location of elevator. Two-way communications shall be directed to a location(s) staffed by authorized personnel who can take appropriate action | 6/14/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | No | No | The monthly fire service testing log has not been updated. | 8/26/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency communications are not working. | 10/16/2025 |