Inspection
Inspection Details
Equipment ID
10635
10635
Inspection Date
12/18/2019
12/18/2019
Inspection Type
Reinspection
Reinspection
Inspector Name
Gary Beadle
Gary Beadle
Mechanic Name
Relief Valve Pressure
NA
NA
Slide
Governor Rope Pull
Door Closing Force
NA
NA
External ID
af88cd66-85d8-45ed-a088-4bc38ac593c5
af88cd66-85d8-45ed-a088-4bc38ac593c5
Location
Holiday Inn- Forest Park
5915 WILSON AVE, SAINT LOUIS, MO
Phone: (314) 645-0700
5915 WILSON AVE, SAINT LOUIS, MO
Phone: (314) 645-0700
Owner
LHM
5915 WILSON AVE, SAINT LOUIS, MO 63110-2711
5915 WILSON AVE, SAINT LOUIS, MO 63110-2711
Billing
Attn: Holiday Inn- Forest Park
5915 WILSON AVE, SAINT LOUIS, MO 63110-2711
5915 WILSON AVE, SAINT LOUIS, MO 63110-2711
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (M) - Car Safeties and Speed Governors | (M)1 | Yes | Yes | Life jacket/plunger gripper would not stop car in the down direction. Unit Red-Tagged. | 1/9/2019 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | No | Unit has a Phase 1 fire service key switch located at the 1st and 2nd floor. The 2nd floor switch does not appear to function. Identify function of the switch or eliminate. | 1/9/2019 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | No | Provide Phase 1 fire service operating instructions on the 1st floor. | 1/9/2019 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | No | Unit has a Phase 1 fire service key switch located at the 1st and 2nd floor. The 2nd floor switch does not appear to function. Identify function of the switch or eliminate. | 5/28/2019 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | No | Provide Phase 1 fire service operating instructions on the 1st floor. | 5/28/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | No | The in car emergency telephone shall work with 24/7 support. | 12/18/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | A written record shall be kept of the quantity of hydraulic fluid added to the system and emptied from leakage collection containers and pans. | 10/25/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning) | No | No | Written evacuation procedures for elevators by authorized persons and emergency personnel shall be available on-site. | 9/2/2022 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | A record of findings for firefighters' service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be available on-site. | 9/2/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(b) On-Site Documentation (Procedures for Inspections and Tests) | No | No | Need procedures for inspections and tests not described in A17.2. | 9/2/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | The disconnect located in the machine space shall be provided with a sign to identify the location of the supply side overcurrent protective device. | 9/2/2022 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone shall be made operable. Re-inspection required | 4/1/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.4 Plunger Gripper Testing | Yes | No | This unit has a plunger gripping device that is supposed to be tested every 5 years and has not been tested since 2018. 5 year full load testing required within 30 days. Re-inspection required | 4/1/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | This unit has an oil recovery system that returns oil that has leaked from the packing back to the pumping unit, this leakage is supposed to be monitored with a 5 gallon bucket. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | This unit has a oil recovery system that returns oil that has leaked from the packing back to the pumping unit, this leakage is supposed to be monitored with a 5 gallon bucket. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | The car door operator cover is missing and shall be reinstalled. |