Inspection
Inspection Details
Equipment ID
17152
17152
Inspection Date
12/20/2019
12/20/2019
Inspection Type
Reinspection
Reinspection
Inspector Name
Gary Beadle
Gary Beadle
Mechanic Name
Relief Valve Pressure
NA
NA
Slide
Governor Rope Pull
Door Closing Force
NA
NA
External ID
5aae6562-a681-4cc3-983c-93c28f50a7bc
5aae6562-a681-4cc3-983c-93c28f50a7bc
Location
Hancock Middle School
243 W RIPA AVE, LEMAY, MO
Phone: (314) 544-6423
243 W RIPA AVE, LEMAY, MO
Phone: (314) 544-6423
Owner
Attn: Hancock Place School District
Hancock Place School District
9417 S BROADWAY, SAINT LOUIS, MO 63125
Phone: (314) 565-0678
Hancock Place School District
9417 S BROADWAY, SAINT LOUIS, MO 63125
Phone: (314) 565-0678
Billing
Attn: Hancock Place School District
Hancock Place School District
9417 S BROADWAY, SAINT LOUIS, MO 63125
Phone: (314) 565-0678
Email: nkanzler@hancock.k12.mo.us
Hancock Place School District
9417 S BROADWAY, SAINT LOUIS, MO 63125
Phone: (314) 565-0678
Email: nkanzler@hancock.k12.mo.us
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | In car emergency light shall work. | 10/12/2018 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | In car emergency alarm bell shall work. | 9/6/2018 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | Yes | The car stop switch shall be bypassed on Phase 1 fire service recall. | 12/12/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | No | The in car emergency telephone shall be operational. | 12/12/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | No | The in car emergency telephone is still not operational. | 12/20/2019 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 7/23/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 9/28/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | The in car emergency alarm bell shall be operational. | 10/24/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | The in car emergency alarm bell is still not operational. | 7/11/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | 2-way communication device shall give proper location message. No location message was given. | 7/26/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.5 Code Data Plate | No | No | There is no code data plate. A correct code data plate shall be provided. |