Inspection
Inspection Details
Equipment ID
14157
14157
Inspection Date
6/21/2018
6/21/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Edward Balsat
Edward Balsat
Mechanic Name
Relief Valve Pressure
320
320
Slide
Governor Rope Pull
Door Closing Force
28
28
External ID
Location
City of St. Louis Refuse
4100 South First St, St. Louis, MO
Phone: (314) 353-8877
4100 South First St, St. Louis, MO
Phone: (314) 353-8877
Owner
St. Louis City Hall
1200 Market St., St. Louis, MO 63103
1200 Market St., St. Louis, MO 63103
Billing
Attn: St. Louis City Hall
1200 Market St., , MO 63103
1200 Market St., , MO 63103
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | Correct door for reliable operation on Phase 1 fire service. | 12/7/2018 |
| conversion | conversion | conversion - reinspect | Yes | No | Replace platen plate rubber isolation pad and secure properly. | 12/7/2018 |
| conversion | conversion | conversion - reinspect | Yes | No | Could not establish connection on emergency phone. | 12/7/2018 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | In car emergency telephone shall work. | 5/29/2020 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | The machine room door shall be self-closing and self-locking. | 6/22/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 6/7/2021 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | The machine room lights shall be operational. | 11/2/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | Yes | No | The door closing force exceeds 30 lbs. and shall be adjusted and re-inspected. | 8/19/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room. | 11/2/2022 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be a means of 2 way communication. The phone seems to be answered, but no one can be heard on the other end. | 8/19/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.11.1.4(b)(2) Hydraulic elevators Placed out of Service | Yes | Yes | This elevator is decommissioned. |