Inspection
Inspection Details
Equipment ID
12539
12539
Inspection Date
1/2/2020
1/2/2020
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Michael Bailey
Michael Bailey
Mechanic Name
Thomas Moore
Thomas Moore
Relief Valve Pressure
Slide
25 1/4
25 1/4
Governor Rope Pull
75/310
75/310
Door Closing Force
20
20
External ID
95efe3e4-6f22-4810-b7f1-bbc85e8abd76
95efe3e4-6f22-4810-b7f1-bbc85e8abd76
Location
Magnolia Hotel
421 N 8TH ST, SAINT LOUIS, MO
Phone: (314) 436-9000
421 N 8TH ST, SAINT LOUIS, MO
Phone: (314) 436-9000
Owner
Magnolia Hotel
818 17TH ST, DENVER, CO 80202-3101
818 17TH ST, DENVER, CO 80202-3101
Billing
Attn: Magnolia Hotel
806 SAINT CHARLES ST, SAINT LOUIS, MO 63101-1500
806 SAINT CHARLES ST, SAINT LOUIS, MO 63101-1500
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | Emergency phone not working on battery | 1/2/2020 |
| conversion | conversion | n/a | No | No | Replace hoist cables | 1/2/2020 |
| conversion | conversion | conversion - reinspect | Yes | No | Emergency alarm not working | 1/2/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency alarm bell does not work on battery back-up. | 1/27/2022 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The pit needs to be cleaned. | 8/18/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Annual inspection not complete. Test car and counterweight buffers. | 1/27/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | The in car emergency lighting shall be operational. | 10/26/2022 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 8/18/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | The in car emergency alarm bell shall be operational. | 8/31/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | The in car emergency light shall be operational. (2nd Notice) | 8/31/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | Yes | No | Replace missing fire tabs on hoistway doors (14th floor). | 10/8/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | A code compliant MCP and all the on-site documentation required shall be provided in the machine room. No MCP and fire service testing logs, which shall be documented monthly. | 4/1/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room door shall be self-closing and self-locking. Latch does not catch strike-plate. | 4/1/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Car top shall be kept clean. | 4/1/2026 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)3 | No | No | Top emergency exit shall be properly secured. The latches are broken. | 4/1/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.7 Cleaning of Hoistway and Pit | No | No | Hoistway doors needs to be cleaned. Door and related hardware are covered in oily lint. | 4/1/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 4/1/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit shall be kept clean and dry. Remove excess debris and repair source of water leak. | 4/1/2026 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)3 | Yes | No | Top emergency exit shall be properly secured. The latches are broken. This item requires a re-inspection as it is a repeat violation. | 4/1/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | A code compliant MCP and all the on-site documentation required shall be provided in the machine room. No MCP and fire service testing logs, which shall be documented monthly. | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room door shall be self-closing and self-locking. Latch does not catch strike-plate. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Car top shall be kept clean. | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)3 | No | No | Top emergency exit shall be properly secured. The latches are broken. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.7 Cleaning of Hoistway and Pit | No | No | Hoistway doors needs to be cleaned. Door and related hardware are covered in oily lint. | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit shall be kept clean and dry. Remove excess debris and repair source of water leak | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)3 | No | No | Top emergency exit shall be properly secured. The latches are broken. This item requires a re-inspection as it is a repeat violation. |