Inspection
Inspection Details
Equipment ID
14167
14167
Inspection Date
1/8/2020
1/8/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michael Bailey
Michael Bailey
Mechanic Name
Marcus Geno
Marcus Geno
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
21
21
External ID
60372fa4-afe2-4ee0-a1f2-79a24ccfb12e
60372fa4-afe2-4ee0-a1f2-79a24ccfb12e
Location
600 Washington Bldg
600 WASHINGTON AVE, SAINT LOUIS, MO
Phone: (314) 231-2252
600 WASHINGTON AVE, SAINT LOUIS, MO
Phone: (314) 231-2252
Owner
Attn: UNK
Cushman & Wakefield
600 WASHINGTON AVE STE 560, SAINT LOUIS, MO 63101
Phone: (000) 000-0000
Cushman & Wakefield
600 WASHINGTON AVE STE 560, SAINT LOUIS, MO 63101
Phone: (000) 000-0000
Billing
Attn: UNK
Cushman & Wakefield
600 WASHINGTON AVE STE 560, SAINT LOUIS, MO 63101
Phone: (314) 925-2180
Email: sarah.kruger@cushwake.com
Cushman & Wakefield
600 WASHINGTON AVE STE 560, SAINT LOUIS, MO 63101
Phone: (314) 925-2180
Email: sarah.kruger@cushwake.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | Doors closing automatically on Phase 2 | 8/23/2018 |
| MO Minimum : Elevators | (K) - Car Platforms and Car Slings | (K)6 | No | No | Replace deteriorating neoprene safety bushings on car sling. | 4/26/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone inoperative. | 2/19/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Replace deteriorating neoprane safety bushings on car sling. | 3/1/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Clean car top of cable lubricating grease & debris | 1/20/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Replace deteriorating neoprene safety rod bushings on car top | 1/20/2026 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | This elevator has a backup emergency generator power that is used in case of a power outage. This system shall be scheduled to be tested and a reinspection is required. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code. Reinspection required. | 2/19/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | There is a bottom guide roller on the counterweight that is worn and shall be replaced. | 1/20/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | The elevator car safety rod bushings have deteriorated and require replacement. | 1/20/2026 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Need to test elevator for operation on emergency power. Re-inspection required | 1/20/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Need to replace deteriorated safety rod bushings on both sides of the elevator | 1/20/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Elevator shall be tested for operation on emergency power. Re-inspection required | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.2 Replacement of Suspension Means (Re-Inspection) | Yes | No | Hoistway Ropes are showing great signs of wear and shall be repaired immediately. |