Inspection
Inspection Details
Equipment ID
7965
7965
Inspection Date
1/13/2020
1/13/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
David Folkert
David Folkert
Mechanic Name
Bobby Joe Mehrens
Bobby Joe Mehrens
Relief Valve Pressure
330
330
Slide
Governor Rope Pull
Door Closing Force
26
26
External ID
9772b008-61c2-4a70-8e34-e8bfacbebc1c
9772b008-61c2-4a70-8e34-e8bfacbebc1c
Location
Buchanan County Courthouse
411 JULES ST, SAINT JOSEPH, MO
Phone: (816) 271-1419
411 JULES ST, SAINT JOSEPH, MO
Phone: (816) 271-1419
Owner
Attn: Kim Hartman
Buchanan, County of
411 JULES ST, SAINT JOSEPH, MO 64501
Phone: (816) 271-1512
Email: khartman@co.buchanan.mo.us
Buchanan, County of
411 JULES ST, SAINT JOSEPH, MO 64501
Phone: (816) 271-1512
Email: khartman@co.buchanan.mo.us
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | Permit needs to be obtained from the state for replacement of hydraulic pumping unit, which has already been replaced. | 1/30/2019 |
| conversion | conversion | conversion - red tag | Yes | Yes | Replaced pumping unit needs acceptance test performed and witnessed by a licensed inspector.. | 1/30/2019 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room access door needs to be self-locking. | 1/15/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.8 Cleaning of Machine Rooms and Machinery Spaces | No | No | Remove non-elevator related material and rags from machine room floor. | 1/15/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.1.6.3 Controllers ,Wiring and Wiring Diagrams | No | No | Install front cover on motor controller enclosure. | 1/15/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 211.8 Switch Keys | No | No | Provide firefighter key on site | 1/15/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.11.1 Firefighters' Emergency Operation & Documentation | No | No | Test and log firefighter operation monthly | 1/15/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Post In Case of Fire Do Not Use Elevator signage next to corridor call station | 1/15/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 211.3a(8) Visual and audible signal | Yes | No | No visual signal during fire recall | 1/13/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.7 Cleaning of Hoistway and Pit | No | No | Remove standing water and oil from pit floor | 1/15/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.7.2 Periodic Test Record (Test Tags) | No | No | Attach metal test tag for periodic test | 1/15/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | No | No | Install cover on starter panel in machine room | 1/15/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 211.8 Switch Keys | No | No | Firefighter key needs to be kept on site | 1/15/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 211.3a(8) Visual and audible signal | No | No | No visual signal during fire recall operation | 2/11/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | Maintenance record log not up to date | 2/11/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | State operating certificate not displayed | 2/11/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 211.3a(8) Visual and audible signal | No | No | Phase 1 jewel on COP not working. | 2/11/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Provide a cover for starter panel in machine room. | 2/11/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | Yes | EMERGENCY LIGHT NOT WORKING | 7/22/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.1 Examination and Maintenance | No | No | REPACK JACK AND CLEAN OIL OVERFLOW FROM PIT | 2/11/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)2 | No | No | FASTEN SPRING STANDS DOWN TO PIT CHANNEL | 2/11/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.1.6.3 Controllers ,Wiring and Wiring Diagrams | No | No | INSTALL COVER ON STARTER PANEL | 2/11/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 211.3a(8) Visual and audible signal | No | No | PROVIDE A WORKING IN CAR FIRE SERVICE JEWEL | 2/11/2026 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | PROVIDE A WORKING EMERGENCY LIGHT & ALARM | 2/11/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.11.1 Firefighters' Emergency Operation & Documentation | No | No | PROVIDE A WORKING PHASE 1 FIRE SERVICE JEWEL |