Inspection
Inspection Details
Equipment ID
2829
2829
Inspection Date
5/3/2018
5/3/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Unknown Conversion
Unknown Conversion
Mechanic Name
Relief Valve Pressure
5609
5609
Slide
Governor Rope Pull
Door Closing Force
External ID
Location
Maryville Treatment Center
30277 US Hwy 136, Maryville, MO
Phone: (660) 582-6542
30277 US Hwy 136, Maryville, MO
Phone: (660) 582-6542
Owner
Maryville Treatment Center
30277 US Hwy 136, Maryville, MO 64468
30277 US Hwy 136, Maryville, MO 64468
Billing
Attn: OA FMDC
301 High St, Room 780, , MO 65102
301 High St, Room 780, , MO 65102
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room access door needs to be self-closing | 9/22/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not operate. | 7/18/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | No | No | No maintenance control plan on site | 9/22/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | No hard copy maintenance records on site | 9/22/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Perform safety test | 7/18/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | Perform overspeed valve test on or before next inspection | 9/22/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(c) On-Site Documentation (Written Checkout Procedures) | No | No | Written checkout procedure for overspeed valve test needs to be kept in the machine room | 9/22/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Perform pressure relief test | 7/18/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | Yes | No | Distance between swing hoistway door and edge of landing sill exceeds .75 inches at the bottom and third landings. A17.1 1996 rule 110.4 | 7/18/2023 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room access door needs to be self-closing. | 9/22/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(c) On-Site Documentation (Written Checkout Procedures) | No | No | Written checkout procedure for overspeed valve needs to be kept in the machine room. | 9/22/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Pit light does not illuminate. | 9/22/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.7.2 Periodic Test Record (Test Tags) | No | No | Install periodic test tag for pressure relief test | 9/22/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | Yes | Yes | Distance between hoistway swing door and the edge of the landing sill exceeds .75 inches at all landings (second notice). A17.1 1996 rule 2500.11 | 12/4/2024 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | IN CAR EMERGENCY PHONE NOT WORKING | 7/30/2025 |