Inspection
Inspection Details
Equipment ID
24550
24550
Inspection Date
12/23/2019
12/23/2019
Inspection Type
Reinspection
Reinspection
Inspector Name
Gary Beadle
Gary Beadle
Mechanic Name
Shane Warth
Shane Warth
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
NA
NA
External ID
9a5fb2a3-71b0-47a0-927d-0709a425a052
9a5fb2a3-71b0-47a0-927d-0709a425a052
Location
St. Louis Aquarium at Union Station
1820 Market St, St. Louis, MO
Phone: (000) 000-0000
Email: stephanie.mcolgan@kone.com
1820 Market St, St. Louis, MO
Phone: (000) 000-0000
Email: stephanie.mcolgan@kone.com
Owner
Attn: Stephanie McOlgan
USH, LLC
111 W Port Plaza, Ste 500, St. Louis, MO 63146
Phone: (000) 000-0000
Email: stephanie.mcolgan@kone.com
USH, LLC
111 W Port Plaza, Ste 500, St. Louis, MO 63146
Phone: (000) 000-0000
Email: stephanie.mcolgan@kone.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.11 - Disconnecting Means and Control | 2.26.4 | x | Provide feeder location on main line and 110v disconnect. | 12/23/2019 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.9 - Floor and emergency identification numbering | 8.11.2.1.3(o) | x | Provide numbering of the car top. | 12/23/2019 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.10 - Numbering of elevators, machines, and disconnect switches | 8.11.2.1.2(j) | x | Provide numbering in the machine room, i.e. controller, main line disconnect, etc. | 12/23/2019 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 8.11.2.1.2(a) | x | Provide machine room door to be UL listed. | 12/23/2019 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 8.11.2.1.2(a) | x | The machine room door shall be self-closing and self-locking. | 12/23/2019 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 8.11.2.1.2(c) | x | Provide code compliant machine room lighting, currently measured at 3.8fc. | 12/23/2019 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.11.2.1.2(g) | x | Provide a current tested fire extinguisher in the elevator machine room. | 12/23/2019 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.4 - Machine space | 8.11.2.1.2(d) | x | Seal all penetrations in the machine room. | 12/23/2019 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.11 - Disconnecting Means and Control | 2.26.4 | x | Provide testing of emergency battery back up system. | 12/23/2019 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.11.2.1.2(e) (Re-Inspection) | x | Clean the machine room. | 12/23/2019 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.8 - Hoistway enclosure | 8.11.2.1.4(h) | x | 1st floor (lobby floor front) floor is not flush and creates a potential tripping hazard. | 12/23/2019 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.13 - Windows, projections, recesses, and setbacks | 8.11.2.1.3(s) | x | Top of hoistway has ledge exceeding 4". Provide means to remove this condition. | 12/23/2019 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.13 - Windows, projections, recesses, and setbacks | 8.11.2.1.3(s) | x | Remove all screws projecting into hoistway walls. | 12/23/2019 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.10 - Hoistway construction | 8.11.2.1.3(p) | x | Seal all penetrations in the hoistway. | 12/23/2019 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | The in car emergency telephone shall work with 24/7 support. | 12/23/2019 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.5 Illumination of Pits | x | Provide code compliant pit lighting, currently measured at 3.9fc. | 12/23/2019 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2 Design and Construction of Pits | x | Provide pit floor to be flush to prevent tripping hazard. | 12/23/2019 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Emergency phone was not answered, phone must be answered 24/7. Re-inspection required | 6/5/2024 | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A copy of the current state operating certificate shall be displayed in the machine room | 1/27/2026 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | Fire extinguisher in control room is expired, replace or have serviced | 1/27/2026 |