Inspection
Inspection Details
Equipment ID
6168
6168
Inspection Date
1/10/2020
1/10/2020
Inspection Type
Reinspection
Reinspection
Inspector Name
Charles Brinkman
Charles Brinkman
Mechanic Name
Richard King
Richard King
Relief Valve Pressure
Slide
N/A
N/A
Governor Rope Pull
N/A
N/A
Door Closing Force
N/A
N/A
External ID
144c2aa4-f517-404a-9134-62d14c3e66e6
144c2aa4-f517-404a-9134-62d14c3e66e6
Location
Dome Building
5400 ARSENAL ST, SAINT LOUIS, MO
Phone: (314) 877-5880
5400 ARSENAL ST, SAINT LOUIS, MO
Phone: (314) 877-5880
Owner
St. Louis Psychiatric Rehab Cntr
5300 ARSENAL ST, SAINT LOUIS, MO 63139-1463
5300 ARSENAL ST, SAINT LOUIS, MO 63139-1463
Billing
Attn: OA FMDC-INTERAGENCY
301 W HIGH-ROOM780, JEFFERSON CITY, MO 65102
301 W HIGH-ROOM780, JEFFERSON CITY, MO 65102
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | 1. Lighting in the machine room shall be not less than ten (10) foot-candles at floor level. The lighting on the upper portion of the machine room, where the machine is located has no lighting. | 12/6/2018 |
| MO Minimum : Elevators | (F) - Electrical Switches | (F)1 | Yes | No | 1) All electric elevators shall have a labeled emergency stop switch. The switch shall be located on or adjacent to the operating panel. There is no stop switch labeled in elevator. Only a door hold button. This shall be corrected. Ref: (F)1 Re-inspect | 1/10/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | Yes | 1) The driving-machine brake shall be maintained to ensure proper operations. When hall door interlock was tripped car continued to move about 2-3 feet. Ref: 8.6.4.6.1 | 7/29/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | 2) Emergency communications shall be tested to determine conformance with the applicable requirements. Phone was tested several times and there was no response to call. Ref: 8.6.4.19.15 | 7/29/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | 3) A written Maintenance Control Program shall be in place to maintain the equipment in compliance with the requirements of Section 8.6. Ref: 8.6.1.2.1 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | 1) A written Maintenance Control Program shall be in place to maintain the equipment in compliance with the requirements of Section 8.6. Ref: 8.6.1.2.1 | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Unit stopped working. | 4/20/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | Car door restrictor is not working. Re-inspection required | 8/2/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | Yes | No | Door restrictor is out of adjustment, repair as needed. | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. |