Inspection
Inspection Details
Equipment ID
5216
5216
Inspection Date
6/20/2018
6/20/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Edward Balsat
Edward Balsat
Mechanic Name
Relief Valve Pressure
Slide
Governor Rope Pull
Door Closing Force
29
29
External ID
Location
Chouteau Building
4030 Chouteau, St. Louis, MO
Phone: (314) 695-6451
4030 Chouteau, St. Louis, MO
Phone: (314) 695-6451
Owner
Summers Properties LLC
1401 S Brentwood Blvd Suite 650, St. Louis, MO 63144
1401 S Brentwood Blvd Suite 650, St. Louis, MO 63144
Billing
Attn: Summers Properties LLC
1401 S Brentwood Blvd Suite 650, , MO 63144
1401 S Brentwood Blvd Suite 650, , MO 63144
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | Alarm bell in hatch does not work. | 3/26/2019 |
| conversion | conversion | conversion - reinspect | Yes | No | Install hoist rope anti-spin cable at car and counterweight. | 3/26/2019 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO state operating certificate shall be posted in the elevator machine room. | 8/7/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | A current tested ABC type fire extinguisher shall be provided in the elevator machine room. | 8/7/2020 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | No | No | The mainline disconnect wireway shall have a cover. | 8/7/2020 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | No | No | Generator wiring shall be enclosed in wireway or conduit. | 8/7/2020 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | The machine room lighting shall be operational. | 4/18/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | A current tested and tagged ABC type fire extinguisher shall be provided in the elevator machine room. | 4/18/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | All the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 4/18/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Testing incomplete due to red tag of other elevator. Need to test: fire service, door pressure, cartop slack selector cable switch, light, bell, phone, pit, bottom door lock, weight portion of test (100% & 125%), slide, runby, pullout/pull-thru, gov electrical/mechanical. | 12/18/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | COP shall have car number displayed (multiple units on-site). | 8/7/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 8/7/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. (2nd Notice) | 8/7/2025 |