Inspection
Inspection Details
Equipment ID
15597
15597
Inspection Date
1/15/2020
1/15/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Clyde Johnson
Clyde Johnson
Mechanic Name
Bill Suedkamp
Bill Suedkamp
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
18
18
External ID
9e2187b7-41ee-4a72-9420-aad6d34496a8
9e2187b7-41ee-4a72-9420-aad6d34496a8
Location
Renaissance Grand Hotel- St. Louis
800 WASHINGTON AVE, SAINT LOUIS, MO
Phone: (314) 621-9600
800 WASHINGTON AVE, SAINT LOUIS, MO
Phone: (314) 621-9600
Owner
Attn: UNK
Marriott St Louis Grand
800 WASHINGTON AVE, SAINT LOUIS, MO 63101
Phone: (314) 418-5840
Email: karen.hinz@marriott.com
Marriott St Louis Grand
800 WASHINGTON AVE, SAINT LOUIS, MO 63101
Phone: (314) 418-5840
Email: karen.hinz@marriott.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | No | No | Repair pit light. | 8/21/2025 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) | Yes | No | Emergency light shall be made operable. Re-inspection required | 12/9/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Elevator machine room shall be self closing and self locking. Door self closing device on floor in machine room. Repair or replace. | 10/16/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | 8.6.4.19.6 Fire service bezel unreadable and shall be replaced. | 10/16/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency communication device not functioning. Phone rings but no one answers. Repair or replace. Reinspection required. | 10/16/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Upon performing the annual inspection, it was noted that no documentation exists even though the inspection tags on the equipment indicate the Category 5 test was completed. Therefore, without any other documentation, it shall be determined that the Category 5 test has not been completed. Either provide documentation from a QEI licensed inspector that the test has been completed or a reinspection shall be required within 15 days to complete the Category 5 test. Failure to comply in this time frame will result in the elevator placed out of service with a red tag issued. | 10/16/2025 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | This elevator has a backup emergency generator power that is used in case of a power outage. This system shall be scheduled to be tested and a reinspection is required. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code. Reinspection required. | 10/16/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Elevator machine room shall be self closing and self locking. Door self closing device on floor in machine room. Repair or replace. | 10/18/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | 8.6.4.19.6 Fire service bezel unreadable and shall be replaced. | 10/18/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency communication device not functioning. Phone rings but no one answers. Repair or replace. 14 days have been given with no repair. | 10/18/2025 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | This elevator has a backup emergency generator power that is used in case of a power outage. This system shall be scheduled to be tested and a reinspection is required. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code. Note: This is part of a Category 5 and Category 1 test. | 10/18/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | Yes | This unit has not had a documented Category 5 test since 2/11/2013. The Category 5 test shall be completed before the elevator can be returned to service. | 10/18/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Elevator machine room shall be self closing and self locking. Door self closing device on floor in machine room. Repair or replace. | 11/5/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | 8.6.4.19.6 Fire service bezel unreadable and shall be replaced. | 11/5/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | Yes | Emergency communication device not functioning. Phone rings but no one answers. Repair or replace. 14 days have been given with no repair. The elevator shall remain out of service until the phone has been repaired. | 11/5/2025 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | Yes | This elevator has a backup emergency generator power that is used in case of a power outage. This system shall be scheduled to be tested and a reinspection is required. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code. Note: This is part of a Category 5 and Category 1 test. | 11/5/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | Yes | This unit has not had a completed Category 5 test since 2/11/2013. The Category 5 test shall be completed before the elevator can be returned to service. To complete this Category 5 requires the emergency power operation test to be completed. | 11/5/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Elevator machine room shall be self closing and self locking. Door self closing device on floor in machine room. Repair or replace. | 4/14/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | 8.6.4.19.6 Fire service bezel unreadable and shall be replaced. | 4/14/2026 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 1002.2g (Standby Power Operation) | Yes | No | Testing of emergency generator shall be scheduled and tested to complete inspection. Re-inspection required | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Elevator machine room shall be self closing and self locking. Door self closing device on floor in machine room. Repair or replace. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | 8.6.4.19.6 Fire service bezel unreadable and shall be replaced. |