Inspection
Inspection Details
Equipment ID
1224
1224
Inspection Date
5/4/2018
5/4/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Paul Karrenbrock
Paul Karrenbrock
Mechanic Name
Relief Valve Pressure
290
290
Slide
Governor Rope Pull
Door Closing Force
24 / 20
24 / 20
External ID
Location
St. Charles High School
725 N Kingshighway St, St. Charles, MO
Phone: (636) 946-1229
725 N Kingshighway St, St. Charles, MO
Phone: (636) 946-1229
Owner
St. Charles R-6 School Dist
2450 Zumbehl Rd, St. Charles, MO 63301
2450 Zumbehl Rd, St. Charles, MO 63301
Billing
Attn: St. Charles R-6 School Dist
2450 Zumbehl Rd, , MO 63301
2450 Zumbehl Rd, , MO 63301
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | x | Emergency phone not working. | 5/23/2019 | |
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | 8.6.1.7.5 - The emergency lowering device (ERU) shall be operational. | 8/19/2021 | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | x | The in car emergency light shall be operational. | 1/4/2021 | |
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | x | The alarm bell shall be operational on main and auxiliary power. | 1/4/2021 | |
MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 8/19/2021 | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 8/19/2021 | ||
MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be obtained and displayed in the elevator machine room. | 8/19/2021 | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | The "G" level hall push button shall be operational. | 8/19/2021 | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room. | |||
MO Minimum : Elevators | (I) - Pits | (I)1 | Clean the pit. Water was pumped out of pit but pit floor needs to be cleaned of oil residue. | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | The bottom limit switch cover is missing and shall be replaced. | |||
MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | |||
MO Minimum : Elevators | (A) - Hoistways | (A)16 | The cover for the limit switch assembly in the pit is missing and shall be replaced. |