Inspection
Inspection Details
Equipment ID
3239
3239
Inspection Date
1/30/2020
1/30/2020
Inspection Type
Reinspection
Reinspection
Inspector Name
Jeffrey Krug
Jeffrey Krug
Mechanic Name
Relief Valve Pressure
n/a
n/a
Slide
Governor Rope Pull
Door Closing Force
n/a
n/a
External ID
41c4b649-d315-4f6c-b1a9-336aacca5055
41c4b649-d315-4f6c-b1a9-336aacca5055
Location
Research Bldg
BLDG 19, ST. LOUIS, MO
Phone: (314) 516-7010
BLDG 19, ST. LOUIS, MO
Phone: (314) 516-7010
Owner
Attn: UMSL
UMSL
1 UNIVERSITY BLVD, SAINT LOUIS, MO 63121
Phone: (314) 516-5937
Email: starkeyjp@umsl.edu
UMSL
1 UNIVERSITY BLVD, SAINT LOUIS, MO 63121
Phone: (314) 516-5937
Email: starkeyjp@umsl.edu
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Emergency light in car doesn't work | 5/21/2026 |
| conversion | conversion | n/a | No | No | Remove water and clean pit | 5/21/2026 |
| conversion | conversion | conversion - reinspect | Yes | No | Phase I fire service - Car returns to wrong floor | 12/19/2019 |
| conversion | conversion | n/a | No | No | Door restrictor doesn't work | 5/21/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Remove water from pit | 5/21/2026 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Telephone in car doesn't work. Phone line dead to controller | 1/30/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency Phone in car fails to establish two-way communication | 5/21/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | All pits shall be kept dry, clean, and free of equipment or material not relating to the operation of the elevator. There is standing water in the pit. | 5/21/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | The pit light does not illuminate | 5/21/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | The emergency phone fails to establish two-way communication. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | Yes | No | Adjust the car door clutch or replace the rail slide guides so the the clutch is not striking the door rollers at every floor |