Inspection
Inspection Details
Equipment ID
15009
15009
Inspection Date
1/10/2020
1/10/2020
Inspection Type
Reinspection
Reinspection
Inspector Name
Michael Ledden
Michael Ledden
Mechanic Name
John Ryan
John Ryan
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
NA
NA
External ID
d547d0d1-7f5c-49b5-b40a-456131beedaa
d547d0d1-7f5c-49b5-b40a-456131beedaa
Location
Grace Lofts
1324 WASHINGTON AVE, SAINT LOUIS, MO
Phone: (314) 588-1170
1324 WASHINGTON AVE, SAINT LOUIS, MO
Phone: (314) 588-1170
Owner
Attn: Grace Lofts
McGowan Brothers
1324 WASHINGTON AVE, SAINT LOUIS, MO 63103-1938
McGowan Brothers
1324 WASHINGTON AVE, SAINT LOUIS, MO 63103-1938
Billing
Attn: McGowan Brothers
Jamie Fite
1314 WASHINGTON AVE STE 300, SAINT LOUIS, MO 63103-1919
Jamie Fite
1314 WASHINGTON AVE STE 300, SAINT LOUIS, MO 63103-1919
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
A17.1-1996 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 1001.2(a)(18) | x | The car door restrictor shall work. | 1/10/2020 | |
A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | The in car emergency lighting shall work. | 1/10/2020 | |
A17.1-1996 : Elevators | 1.3 - Operating control devices | 1001.2(a)(3) | Independent service does not keep the doors open. | 1/10/2020 | ||
A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.2-211.8 | x | x | Phase 2 fire service does not work. Phase 2 fire service shall be repaired and retested. | 1/10/2020 |
A17.1-1996 : Elevators | 5.9 - Buffers and emergency terminal speed limiting devices | 1002.3f | x | Repair the broken conduit on the car buffer switch. | 1/10/2020 | |
MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)2 | The car ceiling is about to fall down. Take corrective action to properly repair the car ceiling. | 9/14/2020 | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | x | Car & hoistway doors need to be adjusted for proper alignment and operation. | 8/12/2021 | |
A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 3/16/2022 | ||
A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) | x | Emergency light inside car does not work. | 10/16/2023 | |
A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Emergency phone does not work. | 10/16/2023 | |
A17.1-1996 : Elevators | 3.23 - Suspension rope | 212 | x | Hoistway ropes are rouged and nearing the minimal allowable diameter and meet the criteria for replacement. | 10/16/2023 | |
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | x | The roller guide on the front left side of the car top while facing the hall doors needs to be replaced. |