Inspection
Inspection Details
Equipment ID
2499
2499
Inspection Date
5/3/2018
5/3/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
David Harris
David Harris
Mechanic Name
Relief Valve Pressure
480
480
Slide
Governor Rope Pull
Door Closing Force
External ID
Location
Chemistry
Rollins & Hitt, Columbia, MO
Phone: (573) 882-6463
Rollins & Hitt, Columbia, MO
Phone: (573) 882-6463
Owner
UMC-General Service
180 General Service Bldg, Columbia, MO 65211
180 General Service Bldg, Columbia, MO 65211
Billing
Attn: UMC- General Service
Campus
180 General Service Bldg, , MO 65211
Campus
180 General Service Bldg, , MO 65211
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | emergency light/bell battery dead | 5/19/2019 |
| MO Minimum : Elevators | (G)2-Alterations | 8.7.2.14.2 Car Enclosure | Yes | No | No active telephone line,no emergency light /alarm | 5/5/2020 |
| MO Minimum : Elevators | (O) - Existing Hydraulic Elevators | (O)4 | No | No | Elevator settling approx 1" IN 15 MIN-close machine room valve | 8/30/2021 |
| MO Minimum : Elevators | (O) - Existing Hydraulic Elevators | (O)4 | No | No | Check control valve for leackback | 8/30/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.5 Code Data Plate | No | No | Provide code data plate conforming to sec 8.9 | 8/30/2021 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (2)(C) Re-Inspection Required to Enforce. | Yes | No | 2021 violation for 2.32 not corrected. Repair/replace valve as needed. REINSPECTION REQUIRED WITHIN 30days | 5/4/2022 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Auxiliary battery lowering is not working. needs repaired. Re-inspection required | 5/14/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | The machine room lighting has been changed to a motion type switch to activate. While this is an energy saving measure, it also is a safety / code concern. Without motion, the switch deactivates the lighting, thereby leaving maintenance personnel with no lighting. Remove motion type switch to a conventional on/off switch. | 8/26/2025 |
| MO Minimum : Elevators | (O) - Existing Hydraulic Elevators | (O)4 | No | No | The elevator control valve seeped an excessive amount of oil in testing. The control valve shall be repaired or replaced | 8/26/2025 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Auxiliary battery lowering is not working, need repaired. Re-inspection required | 8/26/2025 |