Inspection
Inspection Details
Equipment ID
13325
13325
Inspection Date
5/4/2018
5/4/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Paul Karrenbrock
Paul Karrenbrock
Mechanic Name
Relief Valve Pressure
480
480
Slide
Governor Rope Pull
Door Closing Force
25
25
External ID
Location
Residence Inn
3290 Rider Trail South, Earth City, MO
Phone: (314) 209-0995
3290 Rider Trail South, Earth City, MO
Phone: (314) 209-0995
Owner
Residence Inn
3290 Rider Trail South, Earth City, MO 63045
3290 Rider Trail South, Earth City, MO 63045
Billing
Attn: Residence Inn
3290 Rider Trail South, , MO 63045
3290 Rider Trail South, , MO 63045
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 2.35 - Supply Line and Shutoff Valve | 303 | No | No | A hydraulic fitting in the machine room is leaking excessively and shall be repaired. | 6/9/2020 |
| A17.1-1996 : Elevators | 2.5 - Housekeeping | 1001.2(b)(5) | No | No | The elevator machine room cannot be used for storage. Remove the items being stored in the machine room to provide proper room for maintenance to be performed. | 6/9/2020 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1001.2(d)12 | Yes | No | The fireman's emergency service phase I and II operations could not be tested. The elevator door operator was malfunctioning and the maintenance provider placed the unit out of service. | 11/20/2019 |
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | OSV needs to be tested on or before next annual inspection. | 12/12/2022 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.7 Firefighter' Service Operating Procedures | No | No | No fire service instructions next to key switch inside elevator cab | 7/9/2024 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 7/9/2024 |
| A17.1-1996 : Elevators | 2.4 - Machine space | 101.2 | No | No | Remove non elevator related materials from machine room | 7/9/2024 |
| MO Minimum : Elevators | 2.3 - Lighting and receptacles | 110.27 Guarding of Live Parts NFPA 72 | No | No | Repair lights in machine room, wires are exposed. One light is out and fixture or bulbs need to be guarded | 7/9/2024 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.7 Firefighter' Service Operating Procedures | No | No | No fire service instructions next to key switch inside elevator cab. Re-inspection required | 7/9/2024 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency communication inoperable. Re-inspection required | 4/26/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit needs to be cleaned | 7/9/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Cartop needs to be cleaned | 7/9/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Maintenance control program records need to be updated, including monthly fire service checks | 7/9/2024 |
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | No | No | No fire service instructions next to key switch inside elevator cab | 7/9/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Unit not working properly at the time of inspection. | 6/16/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Valve leaking Oil back into tank. Repair or replace as needed. | 8/31/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | State operating certificate shall be displayed in elevator machine room. | 8/31/2025 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency communication inoperable. Phone line has no power, needs repaired. Re-inspection required | |
| A17.1-2016 : Elevators | 1.15 - sign and operating device symbols | 8.6.1.6.7 | No | No | Sign for Phase II instructions is illegible in side car, need to replace with new signage | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Valve leaking oil back into tank, repair or replace as needed |