Inspection
Inspection Details
Equipment ID
11889
11889
Inspection Date
6/20/2018
6/20/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Unknown Conversion
Unknown Conversion
Mechanic Name
Relief Valve Pressure
430
430
Slide
Governor Rope Pull
Door Closing Force
25
25
External ID
Location
Marshall Middle School
565 S O'Dell, Marshall, MO
Phone: (660) 886-6833
565 S O'Dell, Marshall, MO
Phone: (660) 886-6833
Owner
Marshall School District
860 W Vest, Marshall, MO 65340
860 W Vest, Marshall, MO 65340
Billing
Attn: Marshall School District
860 W Vest, , MO 65340
860 W Vest, , MO 65340
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
conversion | conversion | conversion - reinspect | x | fire hat and audible signal did not work in the car operating panel | 5/7/2019 | |
conversion | conversion | conversion - reinspect | x | with the elevator on fire service phase 2 the door open button only worked on the main recall floor. the door open button did not work on the other two floors while in fire service phase 2 operation | 5/7/2019 | |
conversion | conversion | conversion - reinspect | x | the call cancel button did not work on fire service phase 2 operation | 5/7/2019 | |
MO Minimum : Elevators | (S) - Fire Service | (S)1 | x | Repair fire service phase 1 buzzer in the car operating panel, it did not work | 5/15/2020 | |
MO Minimum : Elevators | (S) - Fire Service | (S)1 | x | Repair the fire hat jewel light in the car operating panel, it did not come on during fire service phase 1 recall | 5/15/2020 | |
MO Minimum : Elevators | (S) - Fire Service | (S)1 | x | Repair the call cancel button in the car operating panel, it did not work during fire service phase 2 operation | 5/15/2020 | |
MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | Perform monthly fire service test and post a log in the machine room | 3/26/2021 | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | x | emergency phone did not work, phone line is dead | 8/16/2021 | |
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | elevator will not take a car call for 3rd floor when it is at the 2nd floor | 3/26/2021 | ||
MO Minimum : Elevators | (S) - Fire Service | (S)1 | x | x | fire hat in the car operating panel did not light during phase 1 recall and the audible signal did not sound during phase 1 recall | 8/16/2021 |
A17.1-2016 : Elevators | 1.6 - Car emergency signal | 2.27.1.1.3(h) Two-way communications shall not go to an automated answering system. | x | Phone needs to have 24/7 monitoring | 9/19/2024 |