Inspection
Inspection Details
Equipment ID
1464
1464
Inspection Date
2/5/2020
2/5/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Joseph Jensen
Joseph Jensen
Mechanic Name
Charles Sheriff
Charles Sheriff
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA/NA
NA/NA
Door Closing Force
15
15
External ID
cb2ea743-7c59-4230-b814-258274f87159
cb2ea743-7c59-4230-b814-258274f87159
Location
Centene Place
7711 CARONDELET AVE, CLAYTON, MO
Phone: (314) 565-2824
7711 CARONDELET AVE, CLAYTON, MO
Phone: (314) 565-2824
Owner
Rafco Properties
7700 FORSYTH BLVD STE 100, CLAYTON, MO 63105-1838
7700 FORSYTH BLVD STE 100, CLAYTON, MO 63105-1838
Billing
Attn: CMC Real Estate C/O Rafco Properties
7700 FORSYTH BLVD STE 100VE, CLAYTON, MO 63105-1807
7700 FORSYTH BLVD STE 100VE, CLAYTON, MO 63105-1807
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State operating certificate in machine room | 7/8/2020 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | All the on site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. | 10/6/2025 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 1001.2(a)(17) | Yes | No | The emergency/standby power operation of the elevator shall be tested. | 3/5/2022 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1002.2f | Yes | No | Fire service operation shall be tested. | 3/5/2022 |
| A17.1-1996 : Elevators | 2.11 - Disconnecting Means and Control | 210.4 | No | No | The 120VAC car lighting branch circuit shall not supply the recently installed in-car information displays. | 10/6/2025 |
| A17.1-1996 : Elevators | 2.9 - Guarding of exposed auxiliary equipment | 104.1 | No | No | Kick angles shall be installed around the machine room cable slots to keep items from falling into the hoistway. | 10/6/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | A category 5 test shall be performed. | 3/5/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Fire service operation shall be tested. | 9/20/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | A category 5 test shall be performed. | 9/20/2022 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Alarm bell is not working on emergency power. | 12/31/2025 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 10/6/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Emergency power shall be tested. | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Phase I and PAse II fire service shall be tested. |