Inspection
Inspection Details
Equipment ID
182
182
Inspection Date
1/13/2020
1/13/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
James Mueller
James Mueller
Mechanic Name
Richard Rickermann
Richard Rickermann
Relief Valve Pressure
560
560
Slide
Governor Rope Pull
Door Closing Force
16
16
External ID
bead6cc8-9336-42d2-8fe9-5ddec57a5a35
bead6cc8-9336-42d2-8fe9-5ddec57a5a35
Location
Seckman High School
2800 SECKMAN RD, IMPERIAL, MO
Phone: (636) 282-1485
2800 SECKMAN RD, IMPERIAL, MO
Phone: (636) 282-1485
Owner
Fox C-6 School District
745 JEFFCO BLVD, ARNOLD, MO 63010-1432
745 JEFFCO BLVD, ARNOLD, MO 63010-1432
Billing
Attn: Fox C-6 School District
745 JEFFCO BLVD, ARNOLD, MO 63010-1432
745 JEFFCO BLVD, ARNOLD, MO 63010-1432
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | x | In car emergency telephone shall work. | 1/13/2020 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | In car emergency phone shall be operational. | 1/21/2021 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.11 - Disconnecting Means and Control | 8.11.2.1.2(k) | The disconnect located in the machine space shall be provided with a sign to identify the location of the supply side overcurrent protective device. | 5/27/2025 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.14 - Code data plate | 8.9 | Install a code data plate. It shall read: A17.1-2004. | 5/27/2025 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.8 Machine Rooms and Machinery Spaces | Equipment in the machine room not being used in conjunction with the function or use of the elevator shall be removed. | 5/27/2025 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8.2 (Re-Inspection) | x | Pipes that convey liquid, vapors, or gas and cross overhead or come in close proximity to elevator equipment shall be guttered or guarded | 1/10/2024 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Up to date operating certificate required in the machine room. | 5/27/2025 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 3.26.10 (Auxiliary Power)(Re-Inspection) | x | Auxiliary power lowering does not work. Take corrective action and re-test. | 1/14/2025 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.12 - Car enclosure | 2.14 | 2.14.7.4 - Missing ceiling tiles inside car. | 5/27/2025 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 5/27/2025 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 3.26.10 (Auxiliary Power)(Re-Inspection) | x | Auxiliary power lowering does not work. Take corrective action and re-test. (2nd Notice) | 3/13/2025 |