Inspection
Inspection Details
Equipment ID
15444
15444
Inspection Date
1/28/2020
1/28/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Herbert Neulist
Herbert Neulist
Mechanic Name
Richard King
Richard King
Relief Valve Pressure
500
500
Slide
Governor Rope Pull
Door Closing Force
27
27
External ID
9af43179-30ba-416b-8e66-61768aeb64be
9af43179-30ba-416b-8e66-61768aeb64be
Location
Moolah Temple Apartments
3821 LINDELL BLVD, SAINT LOUIS, MO
Phone: (314) 446-4529
3821 LINDELL BLVD, SAINT LOUIS, MO
Phone: (314) 446-4529
Owner
Moolah Temple Apartments
3821 LINDELL BLVD, SAINT LOUIS, MO 63108-3400
3821 LINDELL BLVD, SAINT LOUIS, MO 63108-3400
Billing
Attn: Coronado Place
3701 LINDELL BLVD, SAINT LOUIS, MO 63108-3425
3701 LINDELL BLVD, SAINT LOUIS, MO 63108-3425
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Replace inoperable emergency alarm bell. | 3/25/2019 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7 | No | No | Replace emergency light. | 1/28/2020 |
| A17.1-1996 : Elevators | 2.1 - Access to machine space | 101.3a | No | No | Elevator machine room shall be locked at all times. | 1/28/2020 |
| A17.1-1996 : Elevators | 2.5 - Housekeeping | 1001.2(b)(5) | No | No | Elevator machine room shall not be used for storage. | 1/28/2020 |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1001.2(b)(7) | No | No | There needs to be a fire extinguisher in the machine room. | 1/28/2020 |
| A17.1-1996 : Elevators | 2.4 - Machine space | 1001.2(b)(4) | No | No | On elevator equipment stored in machine room. | 1/28/2020 |
| A17.1-1996 : Elevators | 2.5 - Housekeeping | 1001.2(b)(5) | No | No | Machine room shall not be used for storage of non elevator related items | 5/30/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | Battery lowering does not work. Repair and reinspect | 5/30/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Full load test needs to be completed. Was due in 2019 | 1/31/2022 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not work. Re-inspection required | 1/9/2024 |
| A17.1-1996 : Elevators | 2.5 - Housekeeping | 1001.2(b)(5) | No | No | Machine room shall not be used for storage. Have been written up multiple times | 5/30/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Battery lowering does not work, repair and re-inspect | 5/30/2025 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Two-way communication device shall work. Multi-year violation. | 2/21/2025 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | Yes | No | Battery lowering shall work. Take corrective action as needed. | 2/21/2025 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required shall be provided in the machine room. | 5/30/2025 |
| A17.1-1996 : Elevators | 2.5 - Housekeeping | 1206.2b (Clean Machine Room) | No | No | Non-elevator related items shall not be stored in the machine room. | 5/30/2025 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 5/30/2025 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 1206.2a (Pits and Hoistways) | No | No | The pit shall be kept clean. Remove excess debris. | 5/30/2025 |
| A17.1-1996 : Elevators | 3.17 - Door and gate equipment | 110 | No | No | Adjust upthrust roller bearings for proper clearance to door hanger track (multiple floors). | 5/30/2025 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7 | No | No | All lamps shall work in the cab. | 5/30/2025 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1206.7 | No | No | Fire service testing shall be documented monthly. | 6/24/2025 |
| A17.1-1996 : Elevators | 2.5 - Housekeeping | 1206.2b (Clean Machine Room) | No | No | Non-elevator related items shall not be stored in machine room. | 6/24/2025 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 6/24/2025 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Two-way communication device shall be operational. | 9/23/2025 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a non-combustible frame with a clear protective vision plate over it. | |
| A17.1-1996 : Elevators | 2.4 - Machine space | 100.3d | No | No | Machine room being used for storage, remove items not essential to elevator operation. |