Inspection
Inspection Details
Equipment ID
15160
15160
Inspection Date
1/15/2020
1/15/2020
Inspection Type
Reinspection
Reinspection
Inspector Name
James Mueller
James Mueller
Mechanic Name
Benjamin Williams
Benjamin Williams
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
NA
NA
External ID
8333b4e5-059b-412a-bcdf-20c024bc1f21
8333b4e5-059b-412a-bcdf-20c024bc1f21
Location
The Saum & Hutcheson Arms Apartments
1919 S GRAND BLVD, SAINT LOUIS, MO
Phone: (314) 685-1130
1919 S GRAND BLVD, SAINT LOUIS, MO
Phone: (314) 685-1130
Owner
Attn: Kali
The Saum & Hutcheson Arms Apartments c/o Sansone Group LLC
120 S Central Ave Suite 500, SAINT LOUIS, MO 63105
Phone: (314) 727-6664
Email: KDurrwachter@sansonegroup.com
The Saum & Hutcheson Arms Apartments c/o Sansone Group LLC
120 S Central Ave Suite 500, SAINT LOUIS, MO 63105
Phone: (314) 727-6664
Email: KDurrwachter@sansonegroup.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | Pit light shall work. | 3/22/2019 | ||
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | Provide adequate machine room lighting. | 3/22/2019 | ||
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | x | Phase 2 fire service shall work. | 10/4/2018 | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | Unable to test the emergency lighting. | 3/22/2019 | ||
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | x | Phase 2 fire service shall work. | 11/13/2018 | |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | x | x | Phase 2 fire service shall be operational. | 1/15/2020 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | Clean the pit. The pit shall be kept clean. | 11/1/2019 | ||
| MO Minimum : Elevators | (I) - Pits | (I)1 | Pit shall be kept clean. | 9/15/2020 | ||
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(a) | Provide MCP | 11/1/2021 | ||
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | Post Phase I instructions near f/f switch | 11/1/2021 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | Phase II halo worn and unreadable | 11/1/2021 | ||
| MO Minimum : Elevators | (I) - Pits | (I)1 | Clean pit | 11/1/2021 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | Sheave seal worn and leaking, repair as needled | 11/1/2021 | ||
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | x | Need to replace defective hoist cables due to excessive rouge & diameter reduction. Re-inspection required in 90 days | 2/26/2025 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | Need to replace missing door gibbs on the 1st, 4th & 8th floors |