Inspection
Inspection Details
Equipment ID
7176
7176
Inspection Date
1/27/2020
1/27/2020
Inspection Type
Reinspection
Reinspection
Inspector Name
Jerry Eckhart
Jerry Eckhart
Mechanic Name
Craig Maupin
Craig Maupin
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
NA
NA
External ID
f0dc43e2-cef8-49fa-8e5d-50874b2d327d
f0dc43e2-cef8-49fa-8e5d-50874b2d327d
Location
Justus Holdings, LLC
1405 PINE ST, SAINT LOUIS, MO
Phone: (314) 698-3060
1405 PINE ST, SAINT LOUIS, MO
Phone: (314) 698-3060
Owner
Attn: Justus Holdings, LLC
Spirit On Pine LP
721 W Hwy 50, O'Fallon, IL 62269
Phone: (314) 361-7067
Email: raj@tutandtut.com
Spirit On Pine LP
721 W Hwy 50, O'Fallon, IL 62269
Phone: (314) 361-7067
Email: raj@tutandtut.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 3.23 - Suspension rope | 1001.2(c)(29) | Yes | No | Suspension ropes are below minimum diameter. Replace and reinspect within 30 days. | 1/27/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | The elevator ADA telephone inside the elevator is not working properly. Two-way communication could not be established. Repair/replace this phone for proper operation and passenger safety. Reinspection required. | 11/25/2025 |
| A17.1-1996 : Elevators | 3.17 - Door and gate equipment | 110 | No | No | The fire tabs (Hoistway Door Safety Retainers) is not installed on the top hoistway door. The fire tab shall be installed to retain the hoistway doors in the closed position if the primary means fails. | 11/25/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | The elevator pit light did not work on the day of inspection, repair for proper illumination of the pit floor. | 11/25/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)7 | No | No | The enclosed stop switch in the pit shall meet A17.1 1995 which requires the switch to be marked red. | 11/25/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | The signage for “In Case of Fire Use Stairs” is not located on the bottom landing. Install signage that conforms to the building code this elevator was installed to meet. | 11/25/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | The fire extinguisher in the machine room shall be serviced, the last annual service tag indicates it was serviced in 2023 | 11/25/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | The elevator car top shall be cleaned of spare parts. | 11/25/2025 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | This elevator has a backup emergency generator power that is used in case of a power outage. This system shall be scheduled to be tested and a reinspection is required. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code. Reinspection required. | 11/25/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.5 Code Data Plate | No | No | There is no code data plate found on the equipment to indicate the code and edition that the elevator was installed to, as used for all inspections. Provide a proper plate on the front of the controller or mainline disconnect. | 11/25/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | The counterweight guides shall be adjusted to provide adequate clearance when the counterweight travels to the top of the hoistway. Currently the guides are rubbing excessively on the guide rail. | 11/25/2025 |
| A17.1-1996 : Elevators | 3.5 - Normal terminal stopping device | 209.2 | Yes | No | The normal terminal stopping device when activated initially stops the car as required. However, after a slight pause, the elevator continues up onto the final limit. Repair and reinspection required in 30 days. | 11/25/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Inspection incomplete, need to perform the following test: emergency generator backup power operation, 125% brake, full speed counterweight buffer, full load, full speed car buffer, full load, full speed car safeties, emergency light, emergency alarm, emergency phone and fire service, after the governor is repaired or replaced. Re-inspection required | 3/18/2026 |
| A17.1-1996 : Elevators | 2.13 - Governor,overspeed switch and seal | 206 | Yes | Yes | Overspeed governor failed jaw/switch speed testing and was Red-tagged, removed from service. Acquire alteration permit, replace governor and rope as needed, and re-test, making sure a data tag with all pertinent information, is permanently attached to governor. Re-inspection required | 3/18/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | The elevator ADA telephone inside the elevator is not working properly. Two-way communication could not be established. Repair or replace the phone for proper operation and passenger safety. Re-inspection required | 3/18/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | The elevator car top shall be cleaned of spare parts. | 3/18/2026 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 1002.2g (Standby Power Operation) | Yes | No | This elevator has a back-up emergency generator power that is used in case of power outage. This system shall be scheduled to be tested and a re-inspection is required. Re-inspection required | 3/18/2026 |
| A17.1-2016 : Elevators | 3.28 - Counterweight and counterweight buffer | 2.21 | No | No | The counterweight guides shall be adjusted to provide adequate clearance when the counterweight travels to the top of the hoistway. Currently the guides are rubbing on the guide rail. | 3/18/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Inspection incomplete, need to perform the following test: emergency generator backup power operation, 125% brake, full speed counterweight buffer, full load, full speed car buffer, full load, full speed car safeties, emergency light, emergency alarm, emergency phone and fire service, after the governor is repaired or replaced. Re-inspection required | 5/26/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency light in car does not work, needs repaired. Re-inspection required | |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 1002.2g (Standby Power Operation) | Yes | No | This elevator has a backup emergency generator power that is used in case of a power outage. This system shall be scheduled to be tested and a re-inspection is required. This requirement is due to the state of Missouri adopting the A17.1.2016 version of the elevator safety code. Re-inspection required |