Inspection
Inspection Details
Equipment ID
14628
14628
Inspection Date
6/1/2018
6/1/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Angelo Consiglio
Angelo Consiglio
Mechanic Name
Relief Valve Pressure
Slide
Governor Rope Pull
Door Closing Force
External ID
Location
Saint Louis Galleria
1155 Saint Louis Galleria, Richmond Heights, MO
Phone: (314) 863-5500
1155 Saint Louis Galleria, Richmond Heights, MO
Phone: (314) 863-5500
Owner
General Growth Properties
1155 Saint Louis Galleria, St. Louis, MO 63117
1155 Saint Louis Galleria, St. Louis, MO 63117
Billing
Attn: General Growth Properties
1155 Saint Louis Galleria, , MO 63117
1155 Saint Louis Galleria, , MO 63117
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.14 | Clean down | 1/15/2020 | ||
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.6 Steps | x | Multiple step tread cleats are damaged, forming a "sharp knife edge". Damaged step treads shall be replaced to conform to code. | 9/24/2024 | |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.11.5.2(i) Demarcation lighting | x | All demarcation lighting shall work. | 9/24/2024 | |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.1 Escalator Handrails | x | Handrails will be free of major cracks and pinch-points. Replace both handrails. | 9/24/2024 | |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.13 Escalator Cleaning | Escalator machine space shall be kept clean and free from excessive debris (dust, dirt, oil, etc.). Clean lower pit. | |||
| Missouri Minimum : Escalators | CSR 40-5.100 State Operating Certificate | 5.100(2) display of certificate | Current state operating permit shall be displayed. | |||
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.3 Step/Skirt Performance Index | x | The skirt index performance test shall be performed. | ||
| Missouri Minimum : Escalators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | The comb impact test shall be performed (If this device exists on this unit, not required until 1992). | ||
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.11.5 Escalator or Moving Walk Startup | A record of authorized personnel trained as specified in 8.6.11.6.2 shall be kept on the premises where the escalators are located and shall be available to the authority having jurisdiction. | |||
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.1.4 Maintenance Records | All the onsite documentation required by A17.1 2016 8.6.1.2.2 and 8.6.1.4 shall be provided on site. | |||
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.13 Escalator Cleaning | The interior and wells shall be cleaned. | |||
| Missouri Minimum : Escalators | CSR 40-5.100 State Operating Certificate | 5.100(2) display of certificate | A current MO State operating certificate shall be posted near the equipment, in a noncombustible frame with a clear protective vision plate over it. | |||
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.6 Steps | x | Damaged or worn step treads shall be replaced. | ||
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.11.5.2(i) Demarcation lighting | x | The top and bottom demarcation lights shall be operational. | ||
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | (T)2 | x | The reversal stop switch (FRD) shall be operational. | ||
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.1 Escalator Handrails | The left handrail is stalling upon startup, this shall be corrected. | |||
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.4 Escalator Combplates | A lower comb segment has a broken tooth and shall be replaced. |