Inspection
Inspection Details
Equipment ID
9741
9741
Inspection Date
6/6/2018
6/6/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
James Mueller
James Mueller
Mechanic Name
Relief Valve Pressure
Slide
instantaneous
instantaneous
Governor Rope Pull
85/500
85/500
Door Closing Force
External ID
Location
5616 Pershing Bldg
5616 Pershing Ave, St. Louis, MO
Phone: (314) 367-5650
5616 Pershing Ave, St. Louis, MO
Phone: (314) 367-5650
Owner
Hamilton Horton 1999 Apts Co LLC
PO Box 410029, St. Louis, MO 63141
PO Box 410029, St. Louis, MO 63141
Billing
Attn: Hamilton Horton 1999 Apts Co LLC
PO Box 410029, , MO 63141
PO Box 410029, , MO 63141
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | A fire extinguisher is required in the elevator machine room. | |||
MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Display the current state operating certificate in the machine room. | |||
MO Minimum : Elevators | (A) - Hoistways | (A)1 | A17.1 - 8.11.2.1.3(t) - The distance from the face of the hoistway doors to the edge of the hoistway landing sills shall not be more than 5". | |||
MO Minimum : Elevators | (C) - Car Enclosure: Freight | (C)4 | The car top shall be metal and shall sustain a load of 200 lbs. applied to any point on the car top. The car top shall be securely fastened and an emergency escape hatch provided. | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | The car top lighting shall be relocated to allow for proper clearance. | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | |||
MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be obtained and displayed in the elevator machine room. | |||
MO Minimum : Elevators | (C) - Car Enclosure: Freight | (C)6 | A "No Passengers" sign shall be posted in the elevator cab. | |||
MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | The machine room lighting shall be not less than 10 foot-candles at floor level. | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | There is no fire extinguisher in the machine room. An ABC type fire extinguisher with a current test tag shall be provided in the machine room. | |||
MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | x | The in car emergency telephone shall be operational. | 5/9/2024 | |
MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | Machine room light shall be at least 10 fc and be guarded. | |||
MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | The machine room door shall be self-closing, self-locking and shall be operable from the interior space without the use of a key. | |||
MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | |||
MO Minimum : Elevators | (C) - Car Enclosure: Freight | (C)6 | A "No Passengers" sign shall be posted in the elevator cab. This is a multi-year violation. Failure to correct the violation may result in unit being red tagged until completed. | |||
MO Minimum : Elevators | (C) - Car Enclosure: Freight | (C)4 | The cartop shall be metal and shall sustain a load of 200 lbs applied to any point on the car top. The car top shall be securely fastened and an emergency escape hatch provided. This is a multi-year violation. Failure to correct the violation may result in unit being red tagged until completed. | |||
MO Minimum : Elevators | (A) - Hoistways | (A)1 | x | The distance from the face of the hoistway doors to the edge of the hoistway landing sills shall not be more than 5". | ||
MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | Machine room light shall be at least 10 fc and be guarded. This is a multi-year violation. Failure to correct the violation may result in unit being red tagged until completed. | |||
MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | The machine room door shall be self-closing and self-locking and shall be operable from the interior space without the use of a key. This is a multi-year violation. Failure to correct the violation may result in unit being red tagged until completed. |