Inspection
Inspection Details
Equipment ID
13424
13424
Inspection Date
2/7/2020
2/7/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michael Bailey
Michael Bailey
Mechanic Name
Richard King
Richard King
Relief Valve Pressure
360
360
Slide
Governor Rope Pull
Door Closing Force
23
23
External ID
2dce0388-9d3b-41c2-9a07-ed976445b451
2dce0388-9d3b-41c2-9a07-ed976445b451
Location
McCormack House
3915 OLIVE ST, SAINT LOUIS, MO
Phone: (314) 531-8844
3915 OLIVE ST, SAINT LOUIS, MO
Phone: (314) 531-8844
Owner
House at Westminster
3915 OLIVE ST, SAINT LOUIS, MO 63108-3196
3915 OLIVE ST, SAINT LOUIS, MO 63108-3196
Billing
Attn: House at Westminister
3915 OLIVE ST, SAINT LOUIS, MO 63108-3196
3915 OLIVE ST, SAINT LOUIS, MO 63108-3196
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | No | No | Provide on-site maintenance control program. | 7/24/2023 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 1001.2(a)(17) | Yes | No | Emergency battery lowering device does not work. | 3/29/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | One bulb in emergency light does not work. | 3/29/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.1 Examination and Maintenance | No | No | When unit was put on ring, excessive fluid leakage from top Vic fitting (below valve) or bottom of valve. Repair as needed. | 7/24/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be properly displayed in machine room. | 7/24/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Replace bad light bulb in emergency light fixture. Reinspect required. | 8/11/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone shall provide two way communications, no one answered. Reinspect required. | 8/11/2023 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 1001.2(a)(17) | Yes | No | Battery lowering system shall work. Reinspect required. | 8/11/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 9/5/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Need to replace bad light bulb in emergency light fixture. Re-inspection required | 10/24/2023 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone shall provide two way communication. Re-inspection required | 10/24/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 11/8/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 5/15/2024 |
| A17.1-1996 : Elevators | 2.32 - Control Valve | 303 | Yes | No | Car failed 15 minute stand test, technician determined that it is leaking back through the valve. | 3/27/2025 |