Inspection
Inspection Details
Equipment ID
13660
13660
Inspection Date
1/22/2020
1/22/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Edward Balsat
Edward Balsat
Mechanic Name
David Howerton
David Howerton
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
29F/20R
29F/20R
External ID
54ace41e-a3c4-4265-bfbd-89a2cb03190c
54ace41e-a3c4-4265-bfbd-89a2cb03190c
Location
St. Louis Language Immersion School
3740 MARINE AVE, SAINT LOUIS, MO
Phone: (314) 776-6300
3740 MARINE AVE, SAINT LOUIS, MO
Phone: (314) 776-6300
Owner
St. Louis Language Immersion School
3740 MARINE AVE, SAINT LOUIS, MO 63118-4175
3740 MARINE AVE, SAINT LOUIS, MO 63118-4175
Billing
Attn: St. Louis Language Immersion School
3740 MARINE AVE, SAINT LOUIS, MO 63118-4175
3740 MARINE AVE, SAINT LOUIS, MO 63118-4175
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display the current state operating certificate in the elevator machine room. | 6/17/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | Provide a current tested ABC type fire extinguisher in the elevator machine room. | 6/17/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 6/19/2020 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | The machine room lighting shall be operational. | 8/31/2022 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | The machine room shall be kept clean. Only elevator related materials and equipment shall be stored in the machine room. | 8/31/2022 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | The in car stop switch shall be overridden while on Phase 1 fire service. | 2/1/2022 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The pit shall be kept clean. Clean the pit. | 8/31/2022 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | The pit lighting shall be operational and a cover installed over the light. | 8/31/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room. | 8/31/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | All the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 8/31/2022 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Lighting in the machine room shall be not less than 10 foot-candles at the floor level. | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | The machine room shall be kept clean. Clean the machine room. | |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The pit shall be kept clean and dry. Clean the pit. | |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | A pit light and a pit light cover shall be provided in the pit. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | An ABC fire extinguisher with a current test tag shall be provided in the machine room. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | All the on-site documentation required by A17.1 2016-8.6.1.2.2 & 8.6.1.4 shall be provided in the machine room. | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Machine room needs more light. Provide code compliant machine room lighting. | |
| MO Minimum : Elevators | (S) - Fire Service | 211.3a(8) Visual and audible signal | Yes | No | Fire hat not lighting up on COP or on hall switch. | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a non-combustible frame with a clear protective vision plate over it. |