Inspection
Inspection Details
Equipment ID
8541
8541
Inspection Date
2/19/2020
2/19/2020
Inspection Type
Reinspection
Reinspection
Inspector Name
Tim Crafton
Tim Crafton
Mechanic Name
Relief Valve Pressure
N/A
N/A
Slide
Governor Rope Pull
Door Closing Force
N/A
N/A
External ID
1a5e0104-aebf-481e-9000-10509026bafe
1a5e0104-aebf-481e-9000-10509026bafe
Location
Saint Louis Galleria
1155 SAINT LOUIS GALLERIA, RICHMOND HEIGHTS, MO
Phone: (314) 863-5500
1155 SAINT LOUIS GALLERIA, RICHMOND HEIGHTS, MO
Phone: (314) 863-5500
Owner
Attn: Saint Louis Galleria
General Growth Properties
1155 SAINT LOUIS GALLERIA, SAINT LOUIS, MO 63117
Phone: (314) 571-7006
Email: nancy.gorman@brookfieldpropertiesretail.com
General Growth Properties
1155 SAINT LOUIS GALLERIA, SAINT LOUIS, MO 63117
Phone: (314) 571-7006
Email: nancy.gorman@brookfieldpropertiesretail.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | Yes | A17.1 2.27.3.3 Phase II Emergency In-Car Operation. NOT WORKING | 2/19/2020 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Place current state operating certificate in machine room. | 12/5/2023 |
| A17.1-1996 : Elevators | 1.4 - Sills and car floor | 1001.2(a)(4) | No | No | Bottom floor landing sill guard needs to be reattached. | 12/5/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 6/3/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning) | No | No | Evacuation procedures are missing from the MCP. | 6/3/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Fire service testing log is missing from the MCP. | 6/3/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | Yes | No | Door restrictor needs to be adjusted. | 6/3/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The pit shall be kept clean and dry. | 6/3/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Phone door is damaged and can not easily be opened. Repair phone door and install a pull handle. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Car top shall be cleaned | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Door Gib on 2nd Floor shall be replaced | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | Door restrictor shall be repaired to prevent doors from opening more than 4" when not at a landing. |