Inspection
Inspection Details
Equipment ID
21349
21349
Inspection Date
1/28/2020
1/28/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Curtis Belew
Curtis Belew
Mechanic Name
Richard Toeniskoetter
Richard Toeniskoetter
Relief Valve Pressure
540
540
Slide
Governor Rope Pull
Door Closing Force
23
23
External ID
cf8c7a07-4286-42d6-9d84-a1173316b139
cf8c7a07-4286-42d6-9d84-a1173316b139
Location
Anna House
12284 DE PAUL DR, BRIDGETON, MO
Phone: (314) 209-8814
12284 DE PAUL DR, BRIDGETON, MO
Phone: (314) 209-8814
Owner
The Sarah Community
12284 DE PAUL DR, BRIDGETON, MO 63044-2508
12284 DE PAUL DR, BRIDGETON, MO 63044-2508
Billing
Attn: The Sarah Community
12284 DE PAUL DR, BRIDGETON, MO 63044-2508
12284 DE PAUL DR, BRIDGETON, MO 63044-2508
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display current state operating certificate. | 10/28/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 10/14/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | This elevator is equipped with an overspeed valve. A category 5 test shall be performed on the overspeed valve on or before the next annual inspection. The valve shall be sealed and tagged after the category 5 test. | 10/14/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | The fire service phase one key-switch bezel shall be legible. Note: The bezel has been punched through the fixture and shall be repaired or replaced. | 10/14/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.5 - Access to Hoistway | 8.6.4.14 Hoistway Access Switches | No | No | The hoistway access switch at the top landing has been punched through the fixture and shall be repaired or replaced. | 10/14/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) | Yes | No | Overspeed valve failed inspection. Unable to set valve within the acceptable range. The category 5 test still needs to be completed. The valve shall be tagged and sealed after being set within the acceptable range. | 2/20/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.11 - Plunger and Cylinder | 8.6.5.5 Gland Packings and Seals | Yes | No | The hydraulic cylinder is leaking oil excessively. Take corrective action as needed. | 2/20/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.11.2.2.6 Fire Fighters Operation (Re-Inspection) | Yes | No | Fire service jewel is missing in hallway. | 2/20/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. | 2/20/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. | 12/28/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Emergency power must be tested annually. (2nd Notice) | 9/9/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 3.26.10 (Auxiliary Power)(Re-Inspection) | Yes | No | Battery lowering unit has been removed and shall be replaced or a variance applied for. See MO Memorandum 016 for more details. | 5/7/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 10/14/2025 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Unit recalled on battery lowering but did not switch to generator power. Elevator equipped to operate on an emergency generator shall be tested annually. | 10/14/2025 |