Inspection
Inspection Details
Equipment ID
18870
18870
Inspection Date
2/11/2020
2/11/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Angelo Consiglio
Angelo Consiglio
Mechanic Name
Thomas Moore
Thomas Moore
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
23
23
External ID
d5a55fac-8b14-458a-bd55-3bac348b91bc
d5a55fac-8b14-458a-bd55-3bac348b91bc
Location
Chase Park Plaza Hotel
212 N KINGSHIGHWAY BLVD, SAINT LOUIS, MO
Phone: (314) 633-1000
212 N KINGSHIGHWAY BLVD, SAINT LOUIS, MO
Phone: (314) 633-1000
Owner
Attn: Chase Park Plaza Royal Sonesta Hotel
Chase Park Plaza Royal Sonesta Hotel
212 N Kingshighway Blvd, St. Louis, MO 63108
Phone: (314) 633-1185
Chase Park Plaza Royal Sonesta Hotel
212 N Kingshighway Blvd, St. Louis, MO 63108
Phone: (314) 633-1185
Billing
Attn: Attn: Accounts Payable
Chase Park Plaza Royal Sonesta Hotel
212 N Kingshighway Blvd, St. Louis, MO 63108
Phone: (314) 633-1185
Email: ssmithhaney@sonesta.com
Chase Park Plaza Royal Sonesta Hotel
212 N Kingshighway Blvd, St. Louis, MO 63108
Phone: (314) 633-1185
Email: ssmithhaney@sonesta.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | replace hoist ropes reaching maximum stretch and rouge (30 days). | 5/1/2019 |
| conversion | conversion | conversion - reinspect | Yes | No | emergency phone not working and bell not working on battery power. | 5/1/2019 |
| conversion | conversion | n/a | No | No | Install code data plate. | 3/31/2026 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | Yes | Suspension ropes are well below minimum diameter and rouged. Elevator taken out of service. | 5/24/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Clean elevator car top. | 3/31/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Repair pit light. | 3/31/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency light and alarm inoperative. | 2/22/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone inoperative on battery back-up power. | 2/22/2021 |
| MO Minimum : Elevators | (A) - Hoistways | (A)1 | No | No | Replace hoistway door sight guards at floor 11. | 3/31/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Repair pit light. | 3/31/2026 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency alarm bell does not work on 110v emergency power. Repair or replace | 4/7/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Fire recall phase one and two shall be tested. Also both buffers and car safeties remain to be tested | 7/28/2023 |
| A17.1-2016 : Elevators | 2.17 - Drive machine brake | 8.6.4.20.10 | Yes | Yes | Car failed to lower and hold 125%. | 9/13/2023 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Provide testing of Phase I operations, record results. | 9/13/2023 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Provide testing of Phase II operations, record results. | 9/13/2023 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency alarm is not working. Re-inspection required | 4/4/2024 |
| MO Minimum : Elevators | (A) - Hoistways | (A)1 | No | No | Replace hoistway door sight guards at floor 11. Initially sited on 2/20. | 3/31/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Clean elevator car top. Initially sited on 5/19. | 3/31/2026 |
| MO Minimum : Elevators | (A) - Hoistways | (A)1 | No | No | Replace hoistway door sight guards at floor 11. Initially sited on 2/20. | 4/3/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Clean elevator car top. Initially sited on 5/19. | 4/3/2026 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | This elevator has a backup emergency generator power that is used in case of a power outage. This system shall be scheduled to be tested and a reinspection is required. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code. Reinspection required. | 5/21/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | The sway guides for the elevator weight compensation chains are worn past their service life and shall be replaced. | 4/3/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | When testing the audible signaling device (alarm bell) with the 110V disconnect in the machine room in the “off” position, the device failed to sound, indicating that either the device is not hooked up to a back-up power device or the back-up power device as failed. Repair for proper operation. Reinspection required. | 6/8/2026 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | This elevator has a backup emergency generator power that is used in case of a power outage. This system shall be scheduled to be tested and a reinspection is required. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code. Reinspection required. | 6/8/2026 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Emergency Power shall be tested | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | No | No | Machine room roof is leaking water into machine room. Patch roof leaks to prevent damage to controllers, machines, and car top. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | Yes | No | Hoist ropes are rouged and undersized and shall be replaced (90 days) reinsp |