A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
phone line for the emergency phone is dead, provide working phone line to the elevator controller
|
5/3/2019
|
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
1206.7
|
|
|
fire service test log is to be filled out monthly, currently only filed in quarterly
|
3/9/2020
|
|
A17.1-2016 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post a copy of the state operating certificate in the elevator machine room
|
2/16/2021
|
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.6.11.1 Firefighters’ Emergency Operation Documentation
|
|
|
monthly fire service test log is not being filled out
|
2/16/2021
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
does not have a 2021 or 2022 maintenance log in the machine room
|
3/1/2022
|
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.6.11.1 Monthly Test and Log
|
|
|
monthly fire service test log has not been filled out
|
3/1/2022
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
emergency phone did not work, phone line is dead, provide working phone line
|
3/29/2023
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
|
|
Machine room fire extinguisher was last inspected in 2022, have the fire extinguisher inspected annually
|
3/20/2024
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.5 - Car lighting and receptacles
|
2.14.7.1.1 Not less than two lamps
|
|
|
Replace burnt out cab ceiling light, required to have two working lightbulbs
|
3/20/2024
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.5 Illumination of Pits
|
|
|
Pit light is burnt out, replace pit light bulb
|
3/20/2024
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)6 (Pit Lighting)
|
|
|
Pit light is burnt out, replace pit light bulb
|
4/28/2025
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.11 - Disconnecting Means and Control
|
8.11.2.1.2(k)
|
|
|
Mark the location of the feeder circuits for the main line and 110 discount in the machine room with the panel and breaker number they are fed from
|
|