Inspection
Inspection Details
Equipment ID
9460
9460
Inspection Date
6/19/2018
6/19/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
John Ryan
John Ryan
Mechanic Name
Relief Valve Pressure
Slide
Governor Rope Pull
Door Closing Force
27
27
External ID
Location
Bank of America Plaza
800 Market St, St. Louis, MO
Phone: (314) 466-6117
800 Market St, St. Louis, MO
Phone: (314) 466-6117
Owner
St. Louis BOA Plaza LP
800 Market St, Ste 301, St. Louis, MO 63101
800 Market St, Ste 301, St. Louis, MO 63101
Billing
Attn: St. Louis BOA Plaza LP
800 Market St, Ste 301, , MO 63101
800 Market St, Ste 301, , MO 63101
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (M) - Car Safeties and Speed Governors | (M)1 | Yes | Yes | Counterweight safety slide was 9" short of the minimum requirement. Unit Red Tagged | 1/22/2020 |
| MO Minimum : Elevators | (D) - Brakes | (D)2 | Yes | Yes | The machine brake would not hold empty car. - Unit Red Tagged | 8/7/2020 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Fire service shall be tested. | 8/7/2020 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Emergency power shall be tested. | 8/7/2020 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Fire service shall be tested. | 8/15/2020 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Emergency power shall be tested. | 8/15/2020 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | Yes | Elevator would not respond to Phase 1 key switch. - Red Tag | 9/4/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 4/1/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Fire service and emergency power operation shall be tested. | 12/4/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Emergency power operation shall be tested. | 7/31/2025 |