Inspection
Inspection Details
Equipment ID
2005
2005
Inspection Date
5/29/2018
5/29/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Unknown Conversion
Unknown Conversion
Mechanic Name
Relief Valve Pressure
n/a
n/a
Slide
Governor Rope Pull
Door Closing Force
25
25
External ID
Location
Cox Medical Center South
3801 S National Ave, Springfield, MO
Phone: (417) 269-4033
3801 S National Ave, Springfield, MO
Phone: (417) 269-4033
Owner
Cox Medical Center
3801 S National Ave, Springfield, MO 65807
3801 S National Ave, Springfield, MO 65807
Billing
Attn: Cox Health Systems
1423 N Jefferson Ave, , MO 65802
1423 N Jefferson Ave, , MO 65802
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | hobble shackles and replace broken spring on CW side | 2/27/2019 |
| conversion | conversion | conversion - reinspect | Yes | No | doorw eill not close on phase I if doors are open when phase i is initiated or will not close on phase II | 2/21/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | 836.1.2.1(2)& 8.6.4.9 clean car top | 12/4/2019 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | H-4 & 8.6.4.8.1 clean machine & machine room | 12/4/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | 8.6.4.13.1(f) 7 8.11.2.1.1(r) door restrictor needs to work | 8/7/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | 8.6.4.7.1 pit needs cleaning | 12/4/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | No | No | Remove covers clean bed plate and driver | 6/15/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | No | telephone line disconnected | 6/29/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | No | Emergency light not working | 6/29/2020 |
| MO Minimum : Elevators | (D) - Brakes | (D)2 | Yes | Yes | A17.1 2016 8.6.4.6.2 (8.6.4.20.4)table passenger elevators must stop and hold 125% | 6/29/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | No | No | clean bed plates and driver | 6/15/2020 |