Inspection
Inspection Details
Equipment ID
20278
20278
Inspection Date
2/10/2020
2/10/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Gary Beadle
Gary Beadle
Mechanic Name
Charles Sheriff
Charles Sheriff
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
20
20
External ID
c05fe83e-6fb1-44dd-82be-1bd9d17b302c
c05fe83e-6fb1-44dd-82be-1bd9d17b302c
Location
University City Senior High School
7401 BALSON AVE, UNIVERSITY CITY, MO
Phone: (314) 290-4100
7401 BALSON AVE, UNIVERSITY CITY, MO
Phone: (314) 290-4100
Owner
University City School District
8136 GROBY RD, UNIVERSITY CITY, MO 63130-2042
8136 GROBY RD, UNIVERSITY CITY, MO 63130-2042
Billing
Attn: University City School District
8136 GROBY RD, UNIVERSITY CITY, MO 63130-2042
8136 GROBY RD, UNIVERSITY CITY, MO 63130-2042
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency phone shall identify the correct elevator car. | 6/4/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.10 - Numbering of elevators, machines, and disconnect switches | 8.11.2.1.2(j) | No | No | Provide correct numbering of car on COP inside the car. | 2/13/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.2 - Stop switches | 8.11.2.1.1(b) (Re-Inspection) | No | No | Car STOP switch is missing from COP. Repair or replace as needed. Test for correct function on Phase 2 fire service. | 10/5/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.11.2.2.6 | Yes | No | 2.26.2.21 - The STOP switch in car is missing and shall be tested for proper function on Phase 2 fire service. | 6/4/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.10 - Numbering of elevators, machines, and disconnect switches | 8.11.2.1.2(j) | No | No | Provide correct numbering of car in machine space on controller, main line disconnect, and 110v disconnect. | 2/13/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.9 - Floor and emergency identification numbering | 8.11.2.1.3(o) | No | No | Provide correct car numbering on car top. | 2/13/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 8.11.2.1.1(q) | Yes | No | The emergency rescue device shall be operational. | 10/5/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 8.11.2.1.2(a) | No | No | The machine room door shall be self-closing, self-locking and shall be operable from the interior space without the use of a key. | 2/13/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 8.11.2.1.2(c) | No | No | The lighting in the overhead shall be functional. | 2/13/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 2/13/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | The pit shall be kept clean. | 2/13/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Battery lowering shall work. Repair or replace. | 6/20/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.17 - Drive machine brake | 2.24.8.4 Means for Manual Release | Yes | No | Repair/replace missing emergency brake release. | 6/20/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Emergency Lighting | Yes | No | Emergency lighting shall work properly. | 6/20/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.2 - Hoistway doors | 8.6.4.13 | Yes | No | Hoistway door safety retainers/fire tabs shall be installed at the bottom of all hoistway doors. | 6/20/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 2.7.5.1 | No | No | Machinery space lighting (top of hoistway) is not working. | 2/13/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Governor set/reset motor shall work. | 2/13/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Compliant/Required documentation shall be kept in the equipment room (neat/organized) including MCP, wiring diagrams, PM log, callback log, and evacuation procedures. Fire service log to be recorded monthly. Logs/MCP not being properly updated. | 2/13/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The phone shall establish 2-way communication. Take corrective action and re-test. | 4/16/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Fire service key switch bezel shall be replaced. The plastic portion is broken. | 4/1/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.42 Seismic (Earthquake protection) | 8.4.10 | No | No | The pit conduit for the seismic wires is rusted through and shall be replaced. | 4/1/2026 |