Inspection
Inspection Details
Equipment ID
22119
22119
Inspection Date
2/24/2020
2/24/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Gary Beadle
Gary Beadle
Mechanic Name
Timothy Cook
Timothy Cook
Relief Valve Pressure
500
500
Slide
Governor Rope Pull
Door Closing Force
25
25
External ID
87544fda-e865-4f16-b5c2-c138d4e949d0
87544fda-e865-4f16-b5c2-c138d4e949d0
Location
Brittany Woods Middle School
8125 GROBY RD, UNIVERSITY CITY, MO
Phone: (314) 290-4280
8125 GROBY RD, UNIVERSITY CITY, MO
Phone: (314) 290-4280
Owner
University City School District
8136 GROBY RD, UNIVERSITY CITY, MO 63130-2042
8136 GROBY RD, UNIVERSITY CITY, MO 63130-2042
Billing
Attn: University City School District
8136 GROBY RD, UNIVERSITY CITY, MO 63130-2042
8136 GROBY RD, UNIVERSITY CITY, MO 63130-2042
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post the current state operating certificate in the elevator machine room. | 2/20/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Provide code compliant MCP on site. | 2/20/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.11 - Disconnecting Means and Control | 2.26.4 | No | No | Provide feeder location on main line and 110v disconnects. | 2/20/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.15 - sign and operating device symbols | 8.11.2.1.1(o) | No | No | Post lobby warning placards at all entrances. | 2/20/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency phone shall be operational with 24/7 support. | 11/10/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO state operating certificate shall be displayed in the elevator machine room. | 2/13/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.5 Illumination of Pits | No | No | The light in the pit shall be repaired. | 2/13/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 2/13/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO state operating certificate shall be displayed in the elevator machine room in a noncombustible frame with a clear protective vision plate over it. | 2/13/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.5 Illumination of Pits | No | No | The pit light shall be operational. | 2/13/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.11 - Disconnecting Means and Control | 2.26.4 | No | No | Feeder locations for the main and lighting branch circuits shall be marked on the disconnects. | 2/13/2024 |