Inspection
Inspection Details
Equipment ID
24655
24655
Inspection Date
12/23/2019
12/23/2019
Inspection Type
Reinspection
Reinspection
Inspector Name
Gary Beadle
Gary Beadle
Mechanic Name
Shane Warth
Shane Warth
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
NA
NA
External ID
b14f3a7f-d6e8-41d2-812b-0e4e30d87fe1
b14f3a7f-d6e8-41d2-812b-0e4e30d87fe1
Location
Farifield Inn & Suites
2144 Market Street, St. Louis, MO
Phone: (000) 000-0000
2144 Market Street, St. Louis, MO
Phone: (000) 000-0000
Owner
Attn: Equis Hospitality Management
Equis Hospitality Management
1401 S. Brentwood Blvd, Ste 575, Brentwood, MO 63114
Phone: (000) 000-0000
Email: kelly.bigby@kone.com
Equis Hospitality Management
1401 S. Brentwood Blvd, Ste 575, Brentwood, MO 63114
Phone: (000) 000-0000
Email: kelly.bigby@kone.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.15 - sign and operating device symbols | 8.11.2.1.1(o) | Yes | No | Provide car number on door buck in lobby. | 12/23/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.15 - sign and operating device symbols | 8.11.2.1.1(o) | Yes | No | Provide lobby warning placards on floors 3R-5R. | 12/23/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.11.2.1.2(g) | Yes | No | Provide a code compliant fire extinguisher at top floor lobby, near elevators. | 12/23/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 8.11.2.1.2(c) | Yes | No | Provide code compliant machine room lighting at top floor. Measured at 14.4fc. | 12/23/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational with 24/7 support. | 12/23/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.8 - Hoistway enclosure | 8.11.2.1.4(h) | Yes | No | Seal all hoistway penetrations. | 12/23/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2 Design and Construction of Pits | Yes | No | Provide sump hole with a cover. | 12/23/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 6/9/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.16 - Traveling cables and junction boxes | 8.11.2.1.3(v) | No | No | The traveling cables shall be installed using an approved method. They are hung incorrectly under the car. | 6/9/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 8.11.2.1.1(q) | Yes | No | 8.6.1.7.5 - The emergency rescue device shall be operational. | 6/17/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 6/9/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.2 - Hoistway doors | 8.6.4.13 | Yes | No | Hoistway doors are missing safety retainers. The top and bottom of horizontally sliding doors shall be provided with a means of retaining the closed door panel in position if the primary guiding means fail. | 12/14/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Hoistways and pits shall be kept free of dirt and rubbish and shall not be used for storage purposes. Clean the pit. | 6/14/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | No | No | The monthly fire service testing log has not been updated. | 8/26/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency communications are not working. | 10/16/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Need oil collection means at bottom of rails; oil leaking onto floor. | 10/16/2025 |